1.
LIEBERT MONITORING GROUP
INSTALLATION &
USER MANUAL
Network Interface Card
O
p
enComms
Vista de página 0
1 2 3 4 5 6 ... 41 42

Resumo do Conteúdo

Página 1 - Network Interface Card

1. LIEBERT MONITORING GROUP INSTALLATION &USER MANUALNetwork Interface Card OpenComms

Página 2

Installation 9 Figure 2. Deluxe System/3 Control Cavity Figure 3. Deluxe System/3 Chilled Water Control Cavity

Página 3

10 Installation Figure 4. ICS Control Cavity

Página 4 - Function Code Support

Installation 11 Figure 5. Challenger Installation Location The OpenComms Network card mounts to the L-plate for Challenger units.

Página 5 - Error Handling

12 Installation System Wiring (SM, AM, AG Microprocessors) Two wiring harnesses are included with the retrofit kit, one for the power connection

Página 6 - Ethernet

Installation 13 Caution: Do NOT tap power from the auxiliary 24VAC terminals T5/G5 on the SM/AM/AG environmental controllers. Damage to controller a

Página 7 - Section 1: INTRODUCTION

14 Installation MiniMate2 and Units Where Internal Mounting is Not Feasible An enclosure is recommended for use with ceiling-mounted environment

Página 8 - SPECIFICATIONS

Installation 15 NPower Installation As a minimum there will be an IFM board (communications interface) mounted at the mid-point on the door. Other

Página 9 - Section 2: INSTALLATION

16 Installation Figure 7. Npower UPS Installation

Página 10 - Installation

Installation 17 USER CONNECTIONS FOR OPENCOMMS NIC Since the OpenComms NIC can use simultaneous connections, Up to 3 user connections are may be req

Página 11 - 10 Installation

18 System Configuration Section 3: SYSTEM CONFIGURATION DIP SWITCH SETTINGS A four-position DIP switch is provided, but no user configuration

Página 13 - 12 Installation

System Configuration 19 Service Terminal Navigat ion Main Menu 1. System Information 1.1 Name 1.2 Contact 1.3 Location 1.4 Description 2.

Página 14 - Microprocessors)

20 System Configuration 1. System Information Menu The System Information Menu seeks descriptive input to enable the unit to be identified. Thi

Página 15 - Feasible

System Configuration 21 is received. When this condition is encountered, pushing the "enter" key returns the unit to the service terminal m

Página 16 - Power Connection for NPower

22 System Configuration 5. Firmware Update Menu The Firmware Update Menu is intended for Liebert service personnel only. No user configurable p

Página 17 - 16 Installation

NIC Setup and Testing 23 Section 4: OPERATION SNMP The OpenComms Network Interface Card supports “get,” “getnext,” “set,” “response” and “trap” p

Página 18

24 NIC Setup and Testing provides the condition ID, the condition description, and the condition time. RFC 1628 UPS MIB UPS units log alarms i

Página 19 - 8 data bits 1 stop bit

NIC Setup and Testing 25 The MIBs for the OpenComms Network Interface Card are available for download on the Liebert Web site, www.liebert.com. Navig

Página 20 - System Configuration

26 NIC Setup and Testing MODBUS RTU See Section 5 for a complete explanation of the Modbus slave. SYSTEM RESET The OpenComms Network card cont

Página 21 - 2. Network Interface Menu

NIC Setup and Testing 27 DS13 IGM Port Transmit DS14-19 Not used Figure 8. LED Locations

Página 22 - 4. Web Server

28 NIC Setup and Testing Section 5: MODBUS COMMUNICATIONS & CONNECTIVITY This section describes the Modbus communications protocol as suppo

Página 23 - 7. Auxiliary Communications

Note To Our Valued Customer To help us better serve you, please contact us with any comments you have about this manual or product in general. W

Página 24 - Section 4: OPERATION

NIC Setup and Testing 29 delay time if HTTP, SNMP and Modbus are going to be utilized simultaneously. TRANSMISSION FORMAT The OpenComms NIC module s

Página 25 - RFC 1628 UPS MIB

30 NIC Setup and Testing Maximum of 32 deviceswith a total cable length of4000feet.Modbus RTU MasterEIA-485 9600,N,8,1Figure 9. Typical Maximum

Página 26 - NIC Setup and Testing

NIC Setup and Testing 31 Maximum of 32 deviceswith a total cable length of4000feet.Modbus RTU MasterEIA-485 9600,N,8,1RMaximum of 32 deviceswith a to

Página 27 - DIAGNOSTICS

32 NIC Setup and Testing A datum should consist of one or multiple registers. The leftmost byte contains the MSB and the rightmost byte contains

Página 28 - Figure 8. LED Locations

NIC Setup and Testing 33 Up to 125 input registers can be read by a single query using function code 0x04. Read, Set Coil Status (0x01, 0x05, 0x0F)

Página 29 - CONNECTIVITY

34 NIC Setup and Testing Exception Response Server Address Function Code (0x80) Exception code 16 bit CRC 1 byte 1 byte 1 bytes 2 bytes Excep

Página 30 - PHYSICAL CONNECTION

NIC Setup and Testing 35 Function Code: The function code field tells the addressed slaves what function to perform. Function codes are specificall

Página 31 - EIA-485 9600,N,8,1

36 NIC Setup and Testing RTU Framing Examples READ REGISTERS (FUNCTION CODE 0X03 & 0X04) Query: for reading holding /input registers (req

Página 32 - MODBUS SLAVE FUNCTIONS

NIC Setup and Testing 37 Section 6: NIC Setup and Testing The NIC has a specific setup that must be in place before the card will function properly.

Página 33

38 NIC Setup and Testing requests. Once the information has been verified, press <escape> to return to the main menu and select “x” to exi

Página 34

Table of Contents Section 1: INTRODUCTION ...6 Specifications...

Página 35 - Modbus Packet Formats

NIC Setup and Testing 39 Once this information is verified, reboot the card and try to access SNMP again. WEB TROUBLESHOOTING If the card does not s

Página 36

40 NIC Setup and Testing Also verify that the proper slave ID has be set in service terminal. Refer to Section 3 for initiating a service termi

Página 37 - (FUNCTION CODE 0X06)

NIC Setup and Testing 41 While every precaution has been taken to ensure accuracy and completeness in this literature, LiebertCorporation assumes no

Página 38 - TESTING THE NETWORK

Read/Write Holding Registers (0x03, 0x06, 0x10)...32 Read Input Registers (0x04)...32 R

Página 39 - SNMP TROUBLESHOOTING

EthernetInternet WebBrowserOpenCommsNICNetwork Management SystemBuilding ManagementSystemModbus EIA-485 Figure 1. Typical Installation

Página 40 - MODBUS TROUBLESHOOTING

6 Installation Section 1: INTRODUCTION The Liebert OpenComms Network Interface Card provides multiple connectivity options for your Liebert equi

Página 41

Installation 7 SPECIFICATIONS Electrical Requirements: Voltage: 18VAC to 24VAC 50/60 Hz, Single Phase 12VDC to 36VDC Power: 6VA maximum Environ

Página 42 - OpenComms NIC

8 Installation Section 2: INSTALLATION The OpenComms NIC card may be ordered as a factory installed option, or in a kit for field retrofit to ex