12MRLDS I&O Manual 026-1307 Rev 4 28-JUN-2011
5.3.6 Wire Connections
Using shielded three-conductor network cable (Belden
#8641 or equivalent), connect the RS485 I/O Network
wire to the three-terminal connector on the Gateway board
as shown in Figure 5-9. For further information about
how RS485 networks are configured, refer to your site
controllers user manual.
To connect the Gateway to an MRLDS, feed the wires
through the rectangular opening in the sensor base as indi-
cated in Figure 1-1. Locate the RS485 connector and
secure the wire leads to the connector orienting them as
shown in Figure 5-10. Connect multiple MRLDS units in
a daisy-chain configuration as shown in Figure 5-1.
5.3.7 Termination Settings
As part of a site controllers RS485 I/O (COM A or
COM D) Network, a Gateway must be terminated if it is
the end device of a daisy chain. The Gateway on the Mod-
bus Network should always be terminated and always
located at the end of the daisy chain.
Refer to the site controllers user manual for informa-
tion about daisy chain networks and how they are termi-
nated.
To terminate the Gateway (the Modbus jumpers should
always
be terminated on the Gateway), set the receiver bus
jumpers to the RIGHT position (Figure 5-11).
5.3.8 Gateway Board I/O Net
Addressing
Set the address on the I/O Network with switches 1-4.
There can be more than one MRLDS Gateway with each
supporting up to 12 MRLDS units.
Switch 5 indicates whether the MRLDS will be
mapped as an IRLDS or 16AI. Set switch 5 to the OFF
position for IRLDS emulation or to the ON position for
16AI emulation.
Figure 5-9
- Connecting the Gateway to the E2 RS485 Network
Figure 5-10 - Connecting the Gateway to MODBUS
GATEWAY BOARD
-485
+485
0v
To MRLDS
MODBUS
A
B
R
S
4
8
5
+
R
S
4
8
5
-
A
C
N
2
4
V
A
C
MRLDS - INSIDE LOWER
PORTION OF BASE
GATEWAY BOARD
+485
-485
0v
+485
-485
0v
E
A
R
T
H
G
N
D
Shield
drain/ground
wire
Shield drain/
ground
wire
MODBUS
NETWORK
Figure 5-11 -MRLDS Gateway Termination
Figure 5-12 - Network Layout Example
RS485
I/O NET
(TO CPC
CONTROLLER)
RS485 I/O NET
TERM JUMPERS
TERMINATION
(ALWAYS
TERMINATE)
14
15
ADDRESS ON
I/O NET
I/O NET MODE
ON = 16AI
OFF = IRLDS