Quick Installation Guide
13
March 2013
Step 3 continued...
FOUNDATION fieldbus
The Rosemount 5300 Series transmitter, FOUNDATION fieldbus version, operates
with a power supply ranging from 9 - 32 Vdc (9 - 30 Vdc in IS applications and 16 -
32 Vdc in Explosion-proof / Flameproof and in Non-Sparking / Energy Limited
applications).
FISCO, IS applications: 9 - 17.5 Vdc.
Non-intrinsically safe power supply
NOTE:
Rosemount 5300 Series Transmitters with Flameproof/Explosion-proof output have a built-in
barrier; no external barrier needed.
Intrinsically safe power supply
Power
Supply
Field Communicator
PC
Rosemount 5300 Series
Transmitter
Fieldbus
Modem
Power
Supply
Approved IS Barrier
Field Communicator
PC
For IS Parameters, see the
Product certifications chapter.
Rosemount 5300 Series
Trans mi tter
Fieldbus
Modem