TESTING & SERVICE
(continued)
2 --- 3
handle
shaft
frame
UP opens the
Emergency source
contacts
DOWN closes the
Emergency source
contacts
UPPER SHAFT
Figure 2–2. Maintenance handle operation for Emergency source contacts (upper shaft).
handle
shaft
frame
UP closes the
Normal source
contacts
DOWN opens the
Normal source
contacts
LOWER SHAFT
Figure 2–3. Maintenance handle operation for Normal source contacts (lower shaft).
Table C. Maintenance handle positions.
Transfer Switch Position
Interlocked Weights
Lobes prevent closing
both N & E contacts
Maintenance Handle Shaft Indicators
E
weight shaft
up
E=O
upper contacts open
orma
N
o
e
weight
shaft
up
N=C
lower contacts closed
Load
E
up
E=O
upper contacts open
Disconnected
N
down
N=O
lower contacts open
E
down
E=C
upper contacts closed
mergency
N
down
N=O
lower contacts open
Comentários a estes Manuais