3B
UPS Systems
57
Table 28 Liebert NXL
with Liebert iCOM Single Module (SMS) - Status and Coil
Data Description
Status
Coil
Number of Bits
Notes
Battery Self Test
10082
-
1
Active on Alarm
Battery Low Shutdown
10092
-
1
Active on Alarm
System Shutdown - REPO
10093
-
1
Active on Alarm
UPS Output on Bypass
10129
-
1
Active on Alarm
Output Load on Maint. Bypass
10132
-
1
Active on Alarm
Main Battery Disconnect Open
10136
-
1
Active on Alarm
Bypass - Excess Auto
Retransfers
10147 - 1 Active on Alarm
Battery Low
10152
-
1
Active on Alarm
System Shutdown - EPO
10157
-
1
Active on Alarm
System Output Off
10158
-
1
Active on Alarm
Battery Over Temperature
10172
-
1
Active on Alarm
Inlet Air Over Temperature
10173
-
1
Active on Alarm
System Input Current Imbalance
10185
-
1
Active on Alarm
System Input Phs Rotation Error
10191
-
1
Active on Alarm
Rectifier Failure
10259
-
1
Active on Alarm
Inverter Failure
10263
-
1
Active on Alarm
Main Controller Fault
10293
-
1
Active on Alarm
Bypass Not Available
10321
-
1
Active on Alarm
Bypass Overload Phase A
10322
-
1
Active on Alarm
Bypass Overload Phase B
10323
-
1
Active on Alarm
Bypass Overload Phase C
10324
-
1
Active on Alarm
Bypass Auto Retransfer Failed
10325
-
1
Active on Alarm
Bypass Static Switch Unavailable
10326
-
1
Active on Alarm
Bypass Static Switch Overload
10327
-
1
Active on Alarm
Bypass Excessive Pulse Parallel
10328
-
1
Active on Alarm
Bypass Auto Transfer Failed
10329
-
1
Active on Alarm
Bypass Frequency Error
10330
-
1
Active on Alarm
Bypass - Manual Rexfr Inhibited
10331
-
1
Active on Alarm
Bypass - Manual Xfr Inhibited
10332
-
1
Active on Alarm
Bypass Static Switch Off Extrnl
10333
-
1
Active on Alarm
Battery Charging Reduced-Extrnl
10334
-
1
Active on Alarm
Battery Capacity Low
10335
-
1
Active on Alarm
Battery Discharging
10336
-
1
Active on Alarm
Battery Temperature Imbalance
10337
-
1
Active on Alarm
Battery Temperature Sensor Fault
10338
-
1
Active on Alarm
Battery Charging Inhibited
10339
-
1
Active on Alarm
Battery Circuit Breaker 1 Open
10340
-
1
Active on Alarm
Battery Circuit Breaker 2 Open
10341
-
1
Active on Alarm