Specifications
44
Table 15 Liebert XDP specifications
Number of Models 4, based on input voltage and pump redundancy
Cooling Capacity, Nominal
160 kW / 46 Tons, 60Hz
140 kW / 40 Tons, 50Hz
Each capacity is based on 45ºF (7ºC) entering water temperature and
140gpm (530lpm) water flow rate. Capacity is reduced when glycol
mixtures are used in place of 100% water.
Electrical Requirements
Input
208V model: 3-phase, 60Hz
460V model: 3 phase, 60Hz
380/420V model: 50Hz
Full Load Amps
208V model: 4A
460V model: 2.1A
380/420V model: 3A
Dimensions, inches (mm)
Height – Unit only 76 (1930) does not include pipe connections
Height – As shipped 83 (2108)
Width 37 (940)
Depth 30 (762)
Weight, lb (kg)
Unit only 855 (388)
Shipping weight 960 (435)
Installed, with coolant and chilled water 1025 (465)
Pipe Connections
XD Coolant supply to XDO or XDV 1-1/8" OD, Cu
XD Coolant return from XDO or XDV 2-1/8" OD, Cu
Chilled water supply and return 2-5/8" OD, Cu
Control valve 2-way, 2" nominal
Pressure Drop – Chilled Water Side
20 PSIG, with 140 gpm (530lpm) water flow rate, control valve fully
open
Temperature Rise – Chilled Water
Side, F (C)
8.0° (4.4°) with rated flow
Number of XDOs Connected Maximum 10; minimum 2
Number of XDVs Connected Maximum 20; minimum 4
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat