Solution:
The server will attempt to update the EFM pointer file periodically, in addition to when the server is shutdown. If
the pointer file cannot be written, the server will re-poll (uploading all EFM data) during the next EFM poll for
meters in the device.
Note:
For more information, refer to the extended error.
Block read for point type <point type>, logical address <logical address>,
parameter range <start parameter - end parameter> of device <device name>
failed. <Error Reason>
Error Type:
Serious
Possible Cause:
The error occurred due to the specified Error Reason.
Solution:
The solution depends on the specified Error Reason.
See Also:
Error Reasons
Device '<device>' responded with error. (Tag '<tag address>')-Details: '<error
code>'
Error Type:
Serious
Possible Cause:
1. The connection between the device and the Host PC is intermittent.
2. The communication parameters for the serial connection are incorrect.
3. Value written is out of range or write was performed while in an incorrect setup area.
Solution:
1. Check the cabling between the PC and the device.
2. Verify that the specified communication parameters match those of the device.
See Also:
Device Setup
Failed to obtain data block for PointType = <point type>, Logical Address =
<address>, Starting Parameter = <starting parameter>, Ending Parameter
<ending parameter> for device '<device>'. Error = <ROC error code>
Error Type:
Serious
Possible Cause:
1. Invalid tag address for point in block.
2. Device not responding.
Solution:
1. Verify the cabling between the PC and the device.
2. Confirm that all tags within this block exist on the device.
See Also:
ROC Error Codes