Infrastructure Management & Monitoring
For Business-Critical Continuity™
Liebert Liqui-tect
®
460
Installation Manual - Zone Leak Detection Sensor
Vista de página 0
1 2 3 4 5 6 ... 15 16

Resumo do Conteúdo

Página 1 - Liebert Liqui-tect

Infrastructure Management & MonitoringFor Business-Critical Continuity™Liebert Liqui-tect® 460Installation Manual - Zone Leak Detection Sensor

Página 2

6Alarm Retest Delay (SS3)SS3 selects the alarm retest delay, the setting in which an alarm is latched and retested every hour.OFF = Non-latching (defa

Página 3 - TABLE OF CONTENTS

7LED OperationSystem Normal (Green):• ON continuously when power is applied to sensor.Alarm Pending (Yellow):• ON continuously during leak detect filt

Página 4

8Installation of Leak Detection System Cable1. Attach the leak detection cable to the LT460 module.2. Activate module and test detection cable. (Touch

Página 5 - Introduction

94. The installation of the hold-down clips should be in pairs according to Figure 5 with the following considerations:Figure 5 Installation of hold-d

Página 6 - Equipment

10Leak Detection Kit Installation ScenariosScenariosUpflow UnitDetection around entire unitUpflow UnitDetection on sides and in front of unitDownflow

Página 8

Ensuring The High AvailabilityOf Mission-Critical Data And Applications.While every precaution has been taken to ensure the accuracy and completeness

Página 10 - Alarm Retest Delay (SS3)

iTABLE OF CONTENTSINTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1EXTERIOR DIMENSIONS AND MOUNTING DETAILS. . .

Página 12

1IntroductionLiebert Liqui-tect® Leak Detection Sensors install quickly and work simply for reliable detection of conductive aqueous fluid leaks.The L

Página 13

2Placement on Subfloor Under Cooling Support Equipment (Other applications such as long perimeter walls can be monitored)As shown above, the Liqui-tec

Página 14

3Power WiringThe LT460 is rated for 24 VAC, 50/60 Hz and 0.12 amp.Figure 1 24V from Liebert environmental units to LT460Figure 2 24V from transformer

Página 15

4Wiring to Auxiliary Alarm PanelsThe LT460 has two Form-C dry contact alarm output contacts (TB2 & TB3). Each contact is rated for 24 VAC at 3 amp

Página 16 - SL-31045_REV5_12-11

5Configuration Switch SettingsA four-position DIP switch is used to select two alarm (filter) delays and three mutually exclusive alarm modes. The swi