Tech ni cal data - LEX14E
DX Ca pac ity (50Hz)*
Out door tem pera ture [°C]
25 30 35 40 45
In door con di tions: 21°C, 50% r.h.
Total cooling capacity kW 14.0 13.5 13.0 12.4 11.8
Sensible cooling capacity kW 13.0 12.8 12.6 12.4 11.8
Compressor absorbed power kW 3.3 3.7 4.1 4.6 5.1
Compressor absorbed current A 7.0 7.4 8.0 8.5 9.1
In door con di tions: 24°C, 50% r.h.
Total cooling capacity
kW 15.1 14.6 13.8 13.3 12.7
Sensible cooling capacity
kW 13.4 13.3 13.0 12.8 12.7
Compressor absorbed power
kW 3.4 3.8 4.2 4.7 5.2
Com pres sor ab sorbed cur rent
A 7.0 7.4 7.9 8.4 9.0
In door con di tions: 27°C, 47% r.h.
Total cooling capacity kW 15.8 15.3 14.7 14.1 13.5
Sensible cooling capacity kW 14.4 14.3 14.1 14.1 13.5
Compressor absorbed power kW 3.4 3.8 4.3 4.8 5.3
Compressor absorbed current A 7.1 7.6 8.0 8.5 9.1
In door con di tions: 30°C, 40% r.h.
Total cooling capacity kW 16.3 15.9 15.4 15.0 14.4
Sensible cooling capacity kW 16.3 15.9 15.4 15.0 14.4
Compressor absorbed power kW 3.5 3.9 4.3 4.8 5.4
Compressor absorbed current A 7.2 7.7 8.1 8.7 9.3
Free cool ing Ca pac ity
Out door tem pera ture [°C]
10 15 20
In door tem pera ture: 21°C
Sensible cooling capacity
kW 11.6 6.3 1.1
In door tem pera ture: 24°C
Sensible cooling capacity kW 14.7 9.5 4.2
In door tem pera ture: 27°C
Sensible cooling capacity
kW 17.9 12.6 7.4
In door tem pera ture: 30°C
Sensible cooling capacity kW 21.1 15.8 10.5
*: Capacities are quoted for R22. For details of R407C capacities, contact Liebert Applications Engine ers.
Note: Quoted capacities are gross capacities, for nett capacities, deduct fan motor kW.
SLE ICX TDM E.2 (06/99) 15