Emerson NXL UPS Systems Manual do Utilizador Página 22

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 48
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 21
Installation Drawings
18
Figure 15 Outline drawing, 250-400kVA, Liebert Module Battery Disconnect
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates.
5. Control wiring and power wiring must be run in seperate conduit.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. Widths are without side panels. The width is 32.1" (815mm) with side panels.
8.The depth dimension includes the front door and rear panel.
CG
76.9
(1952)
33.5
(850)
30.9
(785)
37.9
(962)
14.4
(367)
19.0
(483)
62.3
(1583)
CG
4.1
(104)
Top View
With Door Open
Right Side View
Front View
Vista de página 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 47 48

Comentários a estes Manuais

Sem comentários