ControlWave ExpressPAC Instruction Manual (CI-ControlWave EPAC)
2-6 Installation Revised Mar-2011
If your unit requires a solar panel, you can mount it to the same 2
inch pipe that holds the controller. Make sure there is adequate
clearance for the solar panel. For more information on the solar
panel, see Section 2.3.5.
Only connect power wiring after the unit is mounted and properly
grounded.
I/O wiring, external power wiring, RTD wiring, antenna cabling,
and communication port cabling enters the bottom of the unit
through conduit or special function fittings. (See Figure 2-3.) I/O
wiring is routed through the left side of the unit (right when facing
the front) via a ¾ inch conduit fitting.
Figure 2-3. ControlWave ExpressPAC Bottom View
.