CS400 Series
5
REGULATOR
SLAM-SHUT DEVICE
Overpressure Shutoff (OPSO)
TYPE
Setpoint Spring Range Factory Setpoint
(1)
Spring Range
Spring
Part Number
In. w.c. mbar In. w.c. mbar In. w.c. mbar In. w.c. mbar
CS404
4 10 3.5 to 5 9 to 12 18 45
12 to 25 30 to 60 GF02168X0125 12 4.5 to 6.5 11 to 16 19 47
7 17 6 to 8 15 to 20 21 52
11 27 7.5 to 11 19 to 27 0.9 62
0.58 to 1.6 psig 40 to 110 GF02169X012
14 35 10 to 14 25 to 35 1.1 75
0.65 psig 45 0.45 to 0.7 psig 30 to 47 1.4 psig 96
30 to 44 75 to 110 GF02170X012
0.72 psig 50
0.65 to 1 psig 45 to 69
1.6 psig 112
1 psig 69 2.5 psig 172
1.4 to 4.1 psig 95 to 280 GF02171X012 1.5 psig 103
1 to 2 psig 69 to 138
3.0 psig 207
2 psig 138 3.5 psig 241
3 psig 207
2 to 5.5 psig 138 to 380
6.3 psig 434
3.2 to 11 psig 220 to 760 GF02173X012
4 psig 276 7.3 psig 503
5 psig 345 8.3 psig 572
5.5 psig 380 8.8 psig 606
1. For Types CS404IT and CS404ET equipped with Token Relief, if Non-Factory slam-shut OPSO setpoints are specied, they must not encroach on the Token Relief Start-to-Discharge
values provided in Table 4 of the CS400 Bulletin.
Table 7. Type CS404 Regulator and Slam-shut OPSO Pressure Ranges
REGULATOR SLAM-SHUT DEVICE
TYPE
Setpoint Spring Range
Overpressure Shutoff (OPSO) Underpressure Shutoff (UPSO)
Factory
Setpoint
(1)
Range
Spring Part
Number
Factory
Setpoint
Range
Spring Part
Number
psig mbar psig mbar psig mbar psig mbar psig mbar psig mbar
CS404
0.51 35 0.36 to 0.51 25 to 35 1.1 75
0.73 to 1.9 50 to 130 GF02168X012
0.32 22
0.14 to
1.1
10 to 75 T14169T00120.65 45 0.45 to 0.70 30 to 48 1.4 96 0.4 30
0.72 50
0.65 to 1 45 to 69
1.6 112 1.4 to 3.9 97 to 270 GF02169X012 0.4 30
1 69 2.5 172
2.2 to 5.5 150 to 380 GF02170X012
0.58 40
0.36 to
2.3
25 to
159
T14170T0012 1.5 103
1 to 2
69 to
138
3.0 207 0.73 50
2 138 3.5 241 1 69
3 207
2 to 5.5
138 to
380
6.3 434
3.8 to 8.7 262 to 600 GF02171X012
1.75 121
1.5 to
7.3
100 to
500
FA142869X12
4 276 7.3 503 2 140
5 345 8.3 572
5.8 to 16 400 to 1100 GF02172X012
2.9 200
5.5 380 8.8 606 3.6 250
1. For Types CS404IT and CS404ET equipped with Token Relief, if Non-Factory slam-shut OPSO setpoints are specied, they must not encroach on the Token Relief Start-to-Discharge
values provided in Table 4 of the CS400 Bulletin.
PRIMARY REGULATOR INTEGRAL MONITOR
TYPE
Setpoint
Spring Part
Number
Spring
Color
Setpoint
(1)
Spring Part
Number
Spring Range
Spring
Color
In. w.c. mbar In. w.c. mbar In. w.c. mbar
CS403
4 10 GE30198X012 Red
14 35 GE30189X012 12 to 21 30 to 52 Blue 5 12 GE30195X012 Purple
7 17 GE30188X012 Gold
11 27 GE30189X012 Blue
21 52 GE30196X012 18 to 30 45 to 75 Green
14 35 GE30224X012 Unpainted
18 45 GE30196X012 Green 1 psig 69 GE30225X012 26 to 40 65 to 99 Orange
1 psig 69 GE30225X012 Orange 1.5 psig 103 GE30190X012 1.4 to 2.9 psig 97 to 200 Black
2 psig 138 GE30190X012 Black 2.5 psig 172 GE30190X012 1.4 to 2.9 psig 97 to 200 Black
3 psig 207 GE30197X012
Yellow
3.5 psig 241 GE35081X012 2.6 to 3.7 psig 179 to 255 Purple
4 psig 276 GE30197X012 5 psig 345 GE30192X012 3.6 to 6 psig 248 to 414 Dark Blue
5 psig 345 GE30197X012 6 psig 414 GE33121X012 5.1 to 7.5 psig 352 to 517 Red
1. Integral Monitor setpoints shown represent the minimum setpoint difference between the Integral Monitor and the Primary regulator. Higher monitor setpoints can be chosen, e.g., for
Primary regulator setpoint of 7 in. w.c. / 17 mbar, the Integral Monitor can also be set at 14, 21 in. w.c., 1 psig / 35, 52, 69 mbar or higher.
Table 6. Type CS403 Regulator and Integral Monitor Outlet Pressure Ranges
Table 8. Type CS404 Regulator and Slam-shut OPSO and UPSO Pressure Ranges