CS800 Series
2
Specications
The Specications section lists the specications for the CS800 Series regulators. The following information is stamped on
the regulator at the factory: Type number, date of manufacture, spring range, orice size, maximum inlet pressure, maximum
operating outlet pressure and outlet pressure. Exceeding any of these limits may damage regulator parts.
Available Congurations
See Table 1
Body Sizes, Material, End Connections and
Pressure Ratings
(1)
See Table 3
Maximum Inlet Pressures
(1)
Emergency: 175 psig / 12.1 bar
Operating: See Table 4
Maximum Outlet Pressure
(1)
Emergency
Regulator Casing: 15 psig / 1.0 bar
Integral Monitor Casing: 25 psig / 1.7 bar
Integral Slam-shut Casing: 87 psig / 6.0 bar
To avoid internal parts damage: 3 psig / 0.21 bar
differential above outlet pressure setting
Operating Pressure Ranges
(1)
Regulator: See Table 5
Integral True-Monitor™: See Tables 8 and 9
Slam-shut Module: See Tables 10 to 11
Secondary Seat™
Protection Outlet Pressures
See Table 7
Spring Case Vent Connection
Internal Relief: 1 NPT
High Capacity Relief: 2-1/2 NPT
Internal Relief Performance
See Table 6
Token Relief Performance
Approximate Token Relief Start-to-Discharge:
See Table 6
Orice Sizes, Flow Coefcients and IEC Sizing Coefcients
See Table 4
1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Product has passed Emerson Process Management Regulator Technologies, Inc. (Emerson™) testing for lockup, relief start-to-discharge and reseal down to -40 degrees.
Pressure Registration
Internal or External
Temperature Capabilities
(1)(2)
-20 to 150°F / -30 to 66°C
According to European PED Directive that rates
products to a minimum temperature of -4°F / -20°C
and a maximum temperature of 140°F / 60°C:
-4 to 140°F / -20 to 60°C
Approximate Weight
With Threaded Body
Type CS800/CS820: 25 lbs / 11 kg
Type CS803/CS823: 34 lbs / 16 kg
Type CS804/CS824: 31 lbs / 16 kg
Type CS805/CS825: 26 lbs / 12 kg
Type CS806/CS826: 26 lbs / 12 kg
High-Pressure Types
For CS85x add 2 lbs / 1 kg to types listed above
With Flanged Body
Add 11 lbs / 5 kg to weights listed above
PED Conformity Statement and Information
Types CS800, CS804, CS820, CS824, CS850 and
CS854 are in conformity with the Pressure Equipment
Directive PED 97/23/EC and are classied under
Category I for units without a slam-shut and Category IV
for units with a slam-shut. See Table 2.
For Types CS800, CS820 and CS850, equipment and
pipeline situated on outlet side of the regulator are either
- not subject to the PED (PS ≤ 0.5 bar) or
- subject to (PS > 0.5 bar) in which case they should
come under Category I maximum
PED Related Information
See Table 2
WARNING
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion and/or re
causing property damage and personal injury
or death.
Fisher
®
regulators must be installed, operated
and maintained in accordance with federal,
state and local codes, rules and regulations
and Emerson™ instructions.
If the regulator vents gas or a leak develops in
the system, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition.
Call a gas service person to service the
unit. Only a qualied person must install or
service the regulator.
Description
CS800 Series regulators are typically installed on industrial
and commercial applications. See Table 1 for available
congurations. Constructions with External Registration,
e.g., Type CS800EN, require an external control line.
The CS800 Series offers multiple forms of overpressure
protection including:
Internal Relief - Minimizes downstream pressure buildup
by relieving gas through the diaphragm assembly and
out the 1 NPT vent to atmosphere in the event of an
overpressure situation.