
5
Thermal Expansion Valves
Emerson Climate Technologies
P
1
= 45.5 PSIG
P
2
= 35 PSIG
P
3
= 10.4 PSIG
35 PSIG = 40°F
35 PSIG = 40°F
35 PSIG = 50°F
B
C
TXV with internal
equalizer on evaporator with
no pressure drop.
Fig. 6
A
Superheat
A vapor is said to be superheated whenever its
temperature is higher than the saturation temperature
corresponding to its pressure. The superheat equals the
temperature increase above the saturation temperature
at that pressure. For example, a refrigeration evapora-
tor is operating with R-134a at 35 psig suction pressure
(See g. 6). The R-134a saturation temperature at 35
psig is 40°F. As long as any liquid exists at this pressure,
the refrigerant temperature will remain 40°F as it evapo-
rates or boils off in the evaporator.
suring superheat, install a calibrated pressure gauge in
a gauge connection at the evaporator outlet. In the ab-
sence of a gauge connection, a tee installed in the TXV
external equalizer line can be used just as effectively.
A refrigeration type pocket thermometer with appro-
priate bulb clamp or an electric thermometer with ther-
mocouples may be used to measure gas temperature.
The temperature element from the thermometer
should be taped to the suction line at the point of remote
bulb location and must be insulated. Thermometers will
give an average reading of suction line and ambient if
not insulated. Assuming an accurate gauge and ther-
mometer, this method will provide accurate superheat
readings.
Approximate Methods
of Reading Superheat
When a gauge connection is not available and the
TXV is internally equalized there are two ways of esti-
mating superheat. Neither of these methods will yield an
exact superheat reading.
The rst is the two-temperature method, which uses
the difference in temperature between the evaporator
inlet and outlet as the superheat. The error is caused by
the pressure drop in the evaporator. When the pressure
drop between the evaporator inlet and outlet is 1 psi or
less, the two-temperature method will yield fairly accu-
rate results. But evaporator pressure drop is usually not
known and will vary with load. For this reason, the two-
temperature method cannot be relied on for absolute
superheat readings. The error in this method is negative
and always shows a lower superheat.
The second method involves taking the temperature
at the evaporator outlet and using the compressor suc-
tion pressure as the evaporator saturation pressure. The
error is caused by the pressure drop in the suction line
between the evaporator outlet and the compressor suc-
tion gauge. On packaged equipment and close-coupled
installations, the pressure drop and resulting error are
usually small. But on large built-up systems or systems
with long runs of suction lines, considerable error can
result. Since estimates of suction line pressure drop are
usually not accurate enough to give a true picture of the
superheat, this method cannot be relied on for absolute
values. The error in this method is positive and always
shows a higher superheat.
The only method for checking superheat that will
yield an absolute value involves a pressure and tem-
perature reading at the evaporator outlet.
By realizing the limitations of these approximate
methods and the direction of the error, it is often pos-
As the refrigerant moves along in the coil, the liquid
boils off into a vapor. The liquid is completely evapo-
rated at point B because it has absorbed enough heat to
change the refrigerant liquid to a vapor. The refrigerant
gas continues along the coil and remains at the same
pressure (35 psig); however, its temperature increases
due to continued absorption of heat. When the refriger-
ant gas reaches the end of the evaporator (point “C”) its
temperature is 50°F. This refrigerant gas is now super-
heated and the superheat is 10°F. (50°F minus 40°F).
The amount of superheat depends on how much re-
frigerant is being fed into the evaporator by the TXV and
the heat load to which the evaporator is exposed.
Superheat Adjustment
The function of a TXV is to control the superheat of
the suction gas leaving the evaporator. If superheat is
within reasonable limits, the TXV is operating in a satis-
factory way. If superheat cannot be checked directly, it
is important to know the size and direction of whatever
error is present.
The pressure and temperature of the refrigerant suc-
tion gas passing the TXV remote bulb are required for
an accurate determination of superheat. When mea-
Comentários a estes Manuais