
NetSure™ LMS Data Processing Unit
Installation Instructions, Section 5879 (Issue BA, April 7, 2014)
Spec. No: 58650500, 586505500 Code: Section 5879
Model No: LMS1000 Issue BA, April 7, 2014
Changing the Function Channel Configurations
The function channel configurations can be changed by using the command CONFIG. The command CONFIG is also described in
"Commands" of the User Instructions (Section 5847). Section 5847 can be accessed via the CD (Electronic Documentation Package)
furnished with your system. The command, when entered, will display a header that contains the current configuration. Then,
individually, the command will list each item that can be changed, showing the current information, and then prompting for new or
revised information to be entered. If the current information does not need to be changed, press
ENTER to continue.
Command CONFIG: If the command CONFIG is entered, the system will ask that you identify which channel you wish to modify. Another
way of entering the command is to identify the desired channel in the command line by typing the channel number after the characters
CONFIG (ex. CONFIG F1). The various information pertaining to a function channel that can be changed through this command is
described below. This command is available to users programmed for access to level 6 commands.
Note:
In a 582140000, 582140001, and 582126100 Power System, function channel 64 is dedicated for summing the total current output of
conventional rectifiers in a hybrid application. The channel name for F64 defaults to “Total Rectifier Output.” The LMS updates the MCA
with the calculated value for the configured program line.
Note:
Parameters which apply only to TL1 commands/messages do not appear for configuration if the TL1 software option is not installed.
Type
, then press
.
Channel active (Y or N):
If "Y" is entered, the system will
allow the default configuration
information of the current function
channel to be changed as shown
below.
Type
if the channel is required to be active and
if not, then press
.
If "N" was entered above, the system
responds with...
Set channel configuration to
default values? (Y or N):
Type
to change the attributes of this channel to their default values.
If ”Y” is entered, this command terminates.
If ”N” is entered, the system will allow the default configuration
information of the current function channel to be changed as shown
below.
Name:
Type the desired name for this function channel (30 characters
maximum), then press
.
Sub-access Identifier:
This parameter applies only to TL1 commands/messages. Type the
name (20 characters maximum) of the sub-access identifier that this
channel belongs to, then press
. The group of LMS1000 channels
monitoring a sub-entity in an NMA system should have the same
access identifier and sub-access identifier. Only alpha-numeric
characters can be entered for this parameter. TL1 uses specific values
for this parameter. Refer to TA-NWT-001360, Table 4-1.
System Alarm Report mode (Y or
N):
Type
if the system is required to initiate an alarm report via phone
lines if an alarm limit is exceeded on this channel and
if not, then
press
.
Monitor type:
This parameter applies only to TL1 commands/messages. Type the
name of the unit (10 characters maximum) that the above alarms are
measured in (ex. VOLTDC, CURDC, etc.), then press
. Only alpha
characters can be entered for this parameter. TL1 uses specific values
for this parameter. Refer to TA-NWT-001360 Table 6-1.
Comentários a estes Manuais