SAG584622100, SAG584622200 System Application Guide
SAG584622300, SAG584622400 Spec. Nos. 584622100, 584622200
Issue AC, July 3, 2012 584622300, 584622400 (Model DCS48375)
Page 28 of 34
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
(A) Converter Minor Alarm: Alarms if one converter module fails. Failure conditions
are as follows.
(1) A converter module reports a high voltage shutdown condition (HVSD).
(2) A converter module reports a fan failure.
(3) A converter module reports an EEPROM failure.
(4) A converter module reports a converter failure.
(5) A converter module reports a low input voltage condition.
(6) A converter module reports a high temperature condition.
(7) A converter module reports a thermal derating condition.
(B) Converter Major Alarm: Alarms if more than one converter module fails (or if only one
converter module is installed in the system and it fails). Failure conditions are as stated in
(A) above.
(C) FA/CB Alarm: Alarms if any distribution fuse or circuit breaker opens.
(D) Low Input Voltage: Alarms if a converter module reports a low input voltage condition.