Y695VR Series
2
CONTROL PRESSURE (VACUUM)
OUTLET PRESSURE (VACUUM)
ATMOSPHERIC PRESSURE
B2582
VACUUM BEING
CONTROLLED
HIGHER
VACUUM SOURCE
VACUUM
PUMP
Specications
Body Sizes
3/4 or 1-inch (DN 20 or 25)
End Connection Styles
See Table 2
Maximum (Casing) Pressure
(1)
Full Vacuum
Maximum Downstream Pressure
(1)
Full Vacuum
Vacuum Control Pressure Ranges
(1)
See Table 1
Pressure Registration
Type Y695VR: Internal
Type Y695VRM: External
Orice Size
7/16-inch (11,1 mm)
Control Line Connection
1/2-inch NPT
Material Temperature Capabilities
(1)
Nitrile (NBR): –20° to 180°F (–29° to 82°C)
Fluorocarbon (FKM):
40° to 300°F (4° to 149°C)
Peruoroelastomer (FFKM):
–20° to 300°F (-29° to 149°C)
Spring Case Connection
1/4-inch NPT
Approximate Weight
19 pounds (8,62 kg)
1. The pressure/temperature limits in this instructional manual and any applicable standard or code limitation should not be exceeded.
Figure 2. Type Y695VR Operational Schematic
B2582
INLET CONTROL PRESSURE (VACUUM)
OUTLET PRESSURE (VACUUM)
ATMOSPHERIC PRESSURE (VACUUM)
Comentários a estes Manuais