Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
B-38
(1) This option is only available with range codes 2A and 3A, 316L SST or Alloy C-276 isolating diaphragm and silicone fill fluid.
(2) Performance Class code 3 is available with Measurement Type code D only.
(3) 3051S_CD0 is only available with traditional flange, 316L SST diaphragm material, and Bolting option L4.
(4) Materials of Construction comply with metallurgical requirements highlighted within NACE MR0175/ISO 15156 for sour oil field production environments.
Environmental limits apply to certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining
environments.
(5) Tantalum diaphragm material is only available for ranges 2A - 5A, differential and gage.
(6) Material specified is cast as follows: CF-8M is the cast version of 316 SST, CF-3M is the cast version of 316L SST, CW-12MW is the cast version of Alloy
C-276, M-30C is the cast version of Alloy 400. For housing, material is aluminum with polyurethane paint.
(7) “Assemble to” items are specified separately and require a completed model number. Process connection option codes B12, C11, D11, EA2, EA3, and
EA5 are only available on differential Measurement Type, code D.
(8) Consult an Emerson Process Management representative for performance specifications.
(9) Not available with performance class code 3.
(10) Requires PlantWeb housing.
(11) Available approvals are FM Intrinsically Safe, Division 2 (option code I5), CSA Intrinsically Safe (option code I6), ATEX Intrinsic Safety
(option code I1), and IECEx Intrinsic Safety (option code I7).
(12) Available with output code A only. Available approvals are FM Intrinsically Safe, Division 2 (option code I5), ATEX Intrinsic Safety (option code I1), or IECEx
Intrinsic Safety (option code I7). Contact an Emerson Process Management representative for additional information.
(13) Long-Life Power Module must be shipped separately, order Part #00753-9220-0001.
(14) Not available with output code X.
(15) Requires PlantWeb housing and output code A. Includes Hardware Adjustments as standard.
(16) Requires Rosemount Engineering Assistant to configure.
(17) Not available with process connection option code A11.
(18) Not available with output code F.
(19) Not available with housing style codes 00, 2E, 2F, 2G, 2M, 5A, 5J, or 7J.
(20) Requires PlantWeb housing and Hardware Adjustments option code D1. Limited availability depending on transmitter type and range. Contact an Emerson
Process Management representative for additional information.
(21) Transmitter is shipped with 316 SST conduit plug (uninstalled) in place of standard carbon steel conduit plug.
(22) Valid when SuperModule Platform and housing have equivalent approvals.
(23) Only available with output code X.
(24) Not available with M20 or G ½ conduit entry size.
(25) Only available on differential and gage measurement types. Silicone fill fluid is standard.
(26) Not available with Housing code 7J.
(27) Not available with output code F, option code DA1, or option code QT.
(28) See the 3051S Reference Manual (document number 00809-0100-4801) for cable requirements. Contact an Emerson Process Management
representative for additional information.
(29) P1 is not available with 3051S_CA0.
(30) Requires 316L SST, Alloy C-276, or Gold-plated 316L SST diaphragm material, assemble to Rosemount 305 integral manifold or DIN-compliant traditional
flange process connection, and bolting option L8. Limited to Pressure Range (Differential), ranges 2A – 5A.
(31) Not available with output code F or X. Not available with housing code 7J.
(32) Not available with Housing code 00, 5A, 5J, or 7J.
(33) Requires 316L SST diaphragm material, glass-filled PTFE O-ring (standard), and Process Connection code E12 or F12.
(34) Not available with Housing code 00, 5A, 5J, or 7J. Available with Intrinsically Safe approvals only. For FM Intrinsically Safe, Division 2 (option code I5) or
FM FISCO Intrinsically Safe (option code IE), install in accordance with Rosemount drawing 03151-1009 to maintain outdoor rating (NEMA 4X and IP66).