Reference Manual
00809-0200-4801, Rev CA
July 2010
Rosemount 3051S
3-16
Advanced Features The AI Function Block provides added capability through the addition of the
following parameters:
ALARM_TYPE
ALARM_TYPE allows one or more of the process alarm conditions detected
by the AI function block to be used in setting its OUT_D parameter.
OUT_D
OUT_D is the discrete output of the AI function block based on the detection
of process alarm condition(s). This parameter may be linked to other function
blocks that require a discrete input based on the detected alarm condition.
MULTIPLE ANALOG
INPUT (MAI) FUNCTION
BLOCK
The Multiple Analog Input (MAI) function block has the ability to process up to
eight field device measurements and make them available to other function
blocks. The output values from the MAI block are in engineering units and
contain a status indicating the quality of the measurement.
In the 3051S, the MAI function block is used to read the output statistical
values from the Advanced Diagnostics Transducer Block. The CHANNEL
parameter must be set to 11. The output values are the means and standard
deviations from all four Statistical Process Monitoring (SPM) Blocks.
In Automatic mode, the block’s output parameters (OUT_1 to OUT_8) reflect
the SPM- values and status. In Manual mode, values may be set manually.
The Manual mode is reflected on the output status.
See page 6-11 for further information on using the MAI block to trend
Statistical Process Monitoring data.
Block Errors
Table 3-6 lists conditions reported in the BLOCK_ERR parameter. Conditions
in bold are inactive for the MAI block and are given for reference.
Table 3-6. Block Error
Conditions
Out1 = The block output value and status
for the first channel.
OUT_1
MAI
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
Number Name and Description
0 Other
1 Block Configuration Error: the selected channel carries a measurement that is
incompatible with the engineering units selected in XD_SCALE, the L_TYPE
parameter is not configured, or WRITE_CHECK = zero.
2 Link Configuration Error
3 Simulate Active: Simulation is enabled and the block is using a simulated value in
its execution.
4 Local Override
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input Failure/Process Variable has Bad Status: The hardware is bad, or a bad
status is being simulated.
8 Output Failure: The output is bad based primarily upon a bad input.
9 Memory Failure
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up
15 Out of Service: The actual mode is out of service.