Rosemount 3051
September 2014
www.rosemount.com
Local operator interface
The LOI utilizes a 2 button menu with external configuration
buttons.
Wireless (output code X)
Output
IEC 62591 (WirelessHART), 2.4 GHz DSSS
Wireless radio (internal antenna, WP5 option)
• Frequency: 2.400 - 2.485 GHz
• Channels: 15
• Modulation: IEEE 802.15.4 compliant DSSS
• Transmission: Maximum of 10 dBm EIRP
Local display
The optional 3-line, 7-digit LCD display can display
user-selectable information such as primary variable in
engineering units, scaled variable, percent of range, sensor
module temperature, and electronics temperature. The display
updates based on the wireless update rate.
Digital zero trim
Digital Zero trim (option DZ) is an offset adjustment to
compensate for mounting position effects, up to 5% of URL.
Update rate
User selectable 1 sec. to 60 min.
Wireless sensor module for in-line transmitters
The 3051 Wireless transmitter requires the engineered polymer
housing to be selected. The standard sensor module will come
with aluminum material. If stainless steel is required, the option
WSM must be selected.
Power module
Low power output
1-5 Vdc HART Low Power (output code M)
Output
Three-wire 1-5 Vdc (option code C2) user-selectable output.
Also user selectable for linear or square root output
configuration. Digital process variable superimposed on voltage
signal, available to any host conforming to the HART protocol.
Low-power transmitter operates on 6-12 Vdc with no load.
Power consumption
3.0 mA, 18-36 mW
Minimum load impedance
100 k (V
out
wiring)
Indication
Optional 5-digit LCD display
Overpressure limits
Rosemount 3051CD/CG/CF
• Range 0: 750 psi (51,71 bar)
• Range 1: 2000 psig (137,90 bar)
• Ranges 2-5: 3626 psig (250,00 bar)
4500 psig (310,26 bar) for option code P9
Rosemount 3051CA
• Range 1: 750 psia (51,71 bar)
• Range 2: 1500 psia (103,42 bar)
• Range 3: 1600 psia (110,32 bar)
• Range 4: 6000 psia (413,69 bar)
Rosemount 3051TG/TA
• Range 1: 750 psi (51,71 bar)
• Range 2: 1500 psi (103,42 bar)
• Range 3: 1600 psi (110,32 bar)
• Range 4: 6000 psi (413,69 bar)
• Range 5: 15000 psi (1034,21 bar)
For 3051L or Level Flange Option Codes FA, FB, FC, FD, FP, and
FQ, limit is 0 psia to the flange rating or sensor rating, whichever
is lower.
Static pressure limit
Rosemount 3051CD only
Operates within specifications between static line pressures of
0.5 psia and 3626 psig (4500 psig (310, 26 bar) for Option Code
P9).
Range 0: 0.5 psia and 750 psig (0,03 bar and 51,71 bar)
Range 1: 0.5 psia and 2000 psig (0,03 bar and 137, 90 bar)
Burst pressure limits
3051C, 3051CF Coplanar or
traditional process flange
10081 psig (695,06 bar)
Field replaceable, keyed connection eliminates the risk of
incorrect installation, Intrinsically Safe Lithium-thionyl chloride
Power Module with PBT/PC enclosure. Ten-year life at one
minute update rate.
(1)
(1) Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices.
Note: Continuous exposure to ambient temperature limits of -40 °F or
185 °F (-40 °C or 85 °C) may reduce specified life by less than 20
percent.
Table 9. 3051L and Level Flange Rating Limits
Standard Type CS rating SST rating
ANSI/ASME Class 150 285 psig 275 psig
ANSI/ASME Class 300 740 psig 720 psig
ANSI/ASME Class 600 1480 psig 1440 psig
At 100 °F (38 °C), the rating decreases
with increasing temperature, per ANSI/ASME B16.5.
DIN PN 10-40 40 bar 40 bar
DIN PN 10/16 16 bar 16 bar
DIN PN 25/40 40 bar 40 bar
At 248 °F (120 °C), the rating decreases
with increasing temperature, per DIN 2401.