EZH and EZHSO Series
9
damage, provide pressure-relieving or
pressure-limiting devices to prevent
service conditions from exceeding those
limits. Also, be sure the installation is
in compliance with all applicable codes
and regulations.
Additionally, physical damage to the
regulator could break the pilot off the
main valve, causing personal injury
and property damage due to bursting
of pressure-containing parts. To avoid
such injury and damage, install the
regulator in a safe location.
All Installations
An EZH or EZHSO Series regulator bleeds no gas
to atmosphere during normal operation, thus making
the regulator suitable for installation in pits and other
enclosed locations without elaborate venting systems.
This regulator also can be installed in pits subject to
ooding by venting the pilot spring case above the
expected ood level so that the pilot setting can be
referenced to atmospheric pressure.
1. Only personnel qualied through training and
experience should install, operate and maintain a
regulator. Before installation, make sure that there
is no damage to or debris in the regulator. Also,
make sure that all tubing and piping are clean
and unobstructed.
CAUTION
Eyebolts are installed to aid in the
handling and installation of the Regulator
Assembly only. Do not attempt to lift
more weight than the regulator with
these eyebolts.
2. Install the regulator so that the ow arrow on the
main valve matches the ow direction of process
uid through the regulator.
3. Apply pipe compound to the external pipeline
threads before installing a regulator with threaded
NPT end connections. Use gaskets between
pipeline and regulator anges when installing a
regulator with anged end connections. When
installing butt weld end connections, remove
trim before welding and make sure to use
approved welding practices. Use approved piping
procedures when installing the regulator.
!
WARNING
A regulator may vent some gas to
the atmosphere. In hazardous or
ammable gas service, vented gas may
accumulate, causing personal injury,
death or property damage due to re
or explosion. Install vent line(s) from
the regulator pilot(s) to a remote, safe
location away from air intakes or any
hazardous location. The end of the
vent line or stack opening must be
pointed down and protected against
condensation or clogging.
4. PRX Series pilots have a 1/4 NPT vent connection
in the spring case. The pilot vent opening should
be pointed down. Protect the vent opening from
condensation or clogging. To remotely vent gas
from the spring case, remove the screened vent
and connect 1/4 in. / 6.4 mm piping or tubing to
the spring case connection. The piping or tubing
should vent to a safe location, have as few elbows
as possible and have a screened vent that points
down on its exhaust. Install the regulator and any
remote vent piping or tubing so that the vent is
pointed down and protected from condensation,
freezing or substances that may clog it.
CAUTION
To avoid freeze-up because of pressure
drop and moisture in the gas, use anti-
freeze practices, such as heating the
supply gas or adding a de-icing agent to
the supply gas.
5. The PRX Series pilot connections are 1/4 NPT.
Connect a downstream control (sense) line from
the “A” port on the bottom of the PRX Series pilot
to a straight run of pipe 6 to 10 pipe diameters
from the regulator outlet as shown in Figures 3
and 4, using 3/8 in. / 9.5 mm or larger outside
diameter tubing. If such a distance is not practical,
connect the control line away from elbows,
swages, nipples or any area where abnormal ow
velocities occur.
6. The PRX Series pilot connections are 1/4 NPT.
Connect a downstream bleed line from the “S” port
on the PRX Series pilot with a straight run of pipe
6 to 10 pipe diameters to the regulator outlet as
shown in Figures 3 and 4, using 3/8 in. / 9.5 mm or
larger outside diameter tubing.