6.7 I/O CARD SPECIFICATIONS
Specifications
POWER
Input:
Uses 0.57 W (supplied by MCU), excluding
power consumed by I/O channels connected to field
devices.
Analog Loop:
+T voltage from MCU (24 Vdc when
I/O Converter Card is installed; otherwise, same as
12 or 24 Vdc power to the MCU). Available at “+T”
terminal on each analog input channel.
DISCRETE INPUTS
Quantity/Type:
12 sourced discrete inputs.
Field Wiring Terminals:
“+” positive source voltage,
“-” negative input (common).
Signal Current:
0.5 to 3.5 mA in the active (on)
state, 0 to 0.2 mA in the inactive (off) state.
PULSE COUNTER INPUTS
Quantity/Type:
Four sourced pulse counter inputs.
Field Wiring Terminals:
“+” positive source voltage,
“-” negative input (common).
Signal Current:
0.5 to 3.5 mA in the active (on)
state, 0 to 0.2 mA in the inactive (off) state.
Frequency:
10 kHz maximum.
ANALOG INPUTS
Quantity/Type:
Eight, single-ended voltage-sense
(current loop if supplied scaling resistor is used).
Field Wiring Terminals:
“T” loop power, “+”
positive input, “–” negative input (common).
Voltage:
1 to 5 Vdc, software configurable. 4 to 20
mA, with 250 resistor (supplied) installed across
terminals “+” and “-”.
Accuracy:
0.1% over a -40 to 65 °C (-40 to 149 °F)
range.
Impedance:
One M.
Filter:
Double-pole, low-pass.
Resolution:
12 bits.
DISCRETE OUTPUTS
Quantity/Type:
Six dry-contact SPST relay outputs.
Field Wiring Terminals:
“NO” normally-open
contact; “COM” common.
DISCRETE OUTPUTS (Continued)
Contact Rating:
30 Vdc, 5 A maximum.
Isolation:
1500 volts.
ANALOG OUTPUTS
Quantity/Type:
Two current loop outputs.
Field Wiring Terminals:
“+” positive output and “-”
common.
Range:
4-20 mA with 0 to 22 mA overranging.
Loop Resistance:
300 ohms maximum when +T
is 12 Vdc; 600 ohms maximum when +T is 24 Vdc.
Resolution:
12 bits.
Accuracy:
0.1% of full-scale output.
Settling Time:
100 µs maximum.
Reset Action:
Output goes to zero percent output
or last value (software configurable) on power-up
(warm start) or on watchdog timeout.
DIMENSIONS
0.5 in. D by 5 in. H by 12 in. W (13 mm by 127 mm
by 305 mm).
WEIGHT
1.75 lb. (0.8 kg) nominal.
ENVIRONMENTAL
Operating Temperature:
-40 to 70 °C (-40 to
158 °F).
Storage Temperature:
-50 to 85 °C (-58 to
185 °F).
Operating Humidity:
To 95%, non-condensing.
Vibration:
Designed to meet SAMA 31.1, Cond. 3.
Radiated/Conducted Transmissions:
Complies
with FCC Part 15 Class A.
Voltage Surge Immunity:
Designed to meet IEC
801-4 and EN 61000-4-5.
APPROVAL RATING
Approved by CSA for hazardous locations Class I,
Division 2, Groups A, B, C, and D.