May 2015
10
Quick Start Guide
Figure 7. Transmitter Wiring
A. RL 250 Ω
B. Power supply
Note
Installation of the transient protection terminal block does not provide transient protection unless
the 3051S case is properly grounded.
Signal wiring grounding
Do not run signal wiring in conduit or open trays with power wiring, or near heavy
electrical equipment. Grounding terminations are provided on the sensor module
and inside the Terminal Compartment. These grounds are used when transient
protection terminal blocks are installed or to fulfill local regulations. See Step 2
below for more information on how the cable shield should be grounded.
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 8.
a. The cable shield should:
Be trimmed close and insulated from touching the transmitter housing
Continuously connect to the termination point
Be connected to a good earth ground at the power supply end
Figure 8. Wiring
PlantWeb housing wiring Junction box housing wiring
A. Insulate shield D. Trim shield and insulate
B. Minimize distance E. Safety ground
C. Connect shield back to the power supply ground
A
B
A
B
DP
C
A
B
B
D
E
4801_QIG_RevMA.fm Page 10 Wednesday, May 6, 2015 1:15 PM