Types 66R and 66RR
4
8. Each unit is factory-set for the set pressure specied on
the order. If no setting is specied, set pressure is factory
set at the mid-range of the Type 66R spring (key 6,
Figure 6) or the Type 66RR pilot control spring (key 6,
Figure 8). The set pressure of a unit is adjusted by
changing the compression of the appropriate spring.
Check and verify the spring setting to make sure that it is
correct for the application.
9. Set pressure for a Type 66RR relief valve is dened as
the pressure at which the main valve starts-to-
discharge. Type 66RR units have been designed so
that either a 1-inch w.c. (2,50 mbar) build-up or a
5 percent build-up (whichever is greater) above this set
pressure will open the main valve and permit it to yield
full open capacity.

Key numbers are referenced in Figure 6 for the Type 66R
relief valve, in Figure 7 for the Type 66RR main valve, and in
Figure 8 for the Type 66RR relief valve pilot.
With proper installation and adjustment completed, slowly
open the upstream shutoff valve while using gauges to
monitor pressure. To monitor inlet pressure, remove the pipe
plug (key 31, not shown) on the side of the body opposite
the ow arrow, and then temporarily install a gauge.
On backpressure or bypass applications using an isolating
bypass, also open the downstream shutoff valve and close
the bypass valve.
If set pressure adjustment is necessary, monitor inlet
pressure with a gauge during the adjustment procedure.
Adjust a Type 66R relief valve by removing the closing
cap (key 27) if necessary, loosening the locknut (key 45) if
used, and turning the adjusting screw (key 25) clockwise to
increase or counterclockwise to decrease the set pressure.
After adjustment, tighten the locknut or install the closing
cap. To adjust a Type 66RR relief, remove the Type Y695RR
pilot closing cap (key 22), turn the adjusting screw (key 35)
clockwise to increase or counterclockwise to decrease the
set pressure, and then install the closing cap.


Slowly close the upstream shutoff valve. Release all
pressure from the relief valve, and pilot if used, by opening
the upstream vent valve.

Slowly close the upstream shutoff valve, while opening the
bypass valve if an isolating bypass is used. Then, close the
downstream shutoff valve, and open both vent valves to
release all pressure from the relief valve (and pilot if used).






TAnk



























BJ8921-C
A2562
AV9712-D
A2564
AV9712-D
A2563-1
Figure 3. Type 66R Relief Valve Installation at Outlet
of Sewage Treatment Plant Digester Tank
Figure 4. Type 66RR Relief Valve Installation in
Vacuum Breaker System
Figure 5. Type 66R Relief Valve Installation in
Vacuum Regulation System