Models 644H and 644R Smart
Temperature Transmitters
EN
00810-0177-4728
Rev EA
9/01
Vista de página 0
1 2 3 4 5 6 ... 67 68

Resumo do Conteúdo

Página 1 - Temperature Transmitters

Models 644H and 644R Smart Temperature TransmittersEN00810-0177-4728Rev EA9/01

Página 3 - Temperature Transmitter

SECTION2-1EN2 InstallationSafety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1Tools needed

Página 4

2-2ENRosemount IncFigure 2-1. Installation FlowchartBASIC SETUPSet Sensor TypeSetNumberofWiresSet UnitsSet Range ValuesSet DampingVERIFYSimulate Senso

Página 5 - Table of Contents

2-3ENRosemount IncTOOLS NEEDED FOR INSTALLATIONThe tools needed for installation are as follows:MOUNTINGThe Models 644H and 644R transmitters will ope

Página 6 - Appendix A: Reference Data

2-4ENRosemount IncRetrofitting a Model 644H for Use in an Existing Threaded SensorConnection HeadTo mount a Model 644H in an existing threaded sensor

Página 7 - 1 Introduction

2-5ENRosemount IncHead Mount Transmitter with DIN Plate Style SensorRefer to Volume 2 of the Rosemount Sensors Product Data Sheet (document number 008

Página 8 - MANUAL OVERVIEW

2-6ENRosemount IncHead Mount Transmitter with Threaded SensorRefer to Volume 1 of the Rosemount Sensors Product Data Sheet (document number 00813-0100

Página 9 - Environmental

2-7ENRosemount IncRail Mount Transmitter with Integral Mount SensorRefer to Volume 2 of the Rosemount Sensors Product Data Sheet (document number 0081

Página 10

2-8ENRosemount IncRail Mount Transmitter with Threaded SensorRefer to Volume 1 of the Rosemount Sensors Product Data Sheet (document number 00813-0100

Página 11 - 2 Installation

2-9ENRosemount IncMultichannel InstallationsYou can connect several transmitters to a single master power supply, as shown in Figure 2-8. In this case

Página 13 - MOUNTING

2-10ENRosemount IncUse the following procedure to install the meter.1. If the transmitter is installed in a loop, secure the loop and disconnect the p

Página 14 - Transmitter

2-11ENRosemount IncThe transmitters will accept inputs from a variety of RTD and thermocouple types. Refer to Figure 2-11 on page 2-11 when making sen

Página 15 - 644-0000B04A

2-12ENRosemount IncSENSOR CONNECTIONSRTD or Ohm InputsThe transmitters will accept a variety of RTD configurations, including 2-wire, 3-wire, 4-wire,

Página 16 - Threaded Style Sensor

2-13ENRosemount IncFAILURE MODEChanging Switch PositionsSee Figure 2-11On the Model 644H, the failure mode switch is located on top of the transmitter

Página 17 - 644-0000C04A

2-14ENRosemount Inc

Página 18 - 644-0000A04B

SECTION3-1EN3 OperationSafety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1Power Supply .

Página 19 - LCD Meter Installation

3-2ENRosemount IncSurges and TransientsTo protect against high-energy transients, install the transmitter into a suitable connection head with the Ros

Página 20 - FIELD WIRING

3-3ENRosemount IncFigure 3-2. HART Communicator Menu TreeNOTEThe review menu lists allof the information storedin the Model 644. Thisincludes devicein

Página 21 - 1260B02D

3-4ENRosemount IncTable 3-1. Model 644 Fast Key SequenceFunctionsHARTCommunicatorFast KeysFunctionsHARTCommunicatorFast KeysActive Calibrator 1, 2, 2,

Página 22 - RTD or Ohm Inputs

SECTION4-1EN4 Hardware and Software Maintenance and TroubleshootingSafety Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 23 - Changing Switch Positions

Model 644 Smart Temperature TransmitterModel 644 Revision: 5.5.2, 5.5.3, 5.5.4HART® Communicator Field Device Revision: Dev v5, DD v2Rosemount®Models

Página 24

4-2ENRosemount IncTABLE 4-2. Hardware diagnostic messagesSymptomPotentialSourceCorrective ActionTransmitterDoes NotCommunicatewith HARTCommunicatorLoo

Página 25 - 3 Operation

4-3ENRosemount IncLow Output orNo OutputSensorElement• Connect a HART-based communicator and enter theTransmitter test mode to isolate a sensor failur

Página 26 - Hart Fast Key Feature

4-4ENRosemount IncModel 275 HART CommunicatorTable 4-3 provides a guide to diagnostic messages used by the Model 275 HART Communicator (HC).Variable p

Página 27

4-5ENRosemount IncIllegal date The day portion of the date is invalid.Illegal month The month portion of the date is invalid.Illegal year The year por

Página 28

4-6ENRosemount IncSavedatafromdevicetoconfiguration memoryPrompts user to press SAVE softkey to initiate a device-to-memorytransfer.Saving data toconf

Página 29 - Hardware

4-7ENRosemount IncLCD MeterIn addition to the output, the LCD meter displays abbreviated diagnostic messages for troubleshooting the transmitter. To d

Página 30

4-8ENRosemount IncOFLOW The location of the decimal point, as configured in the meter setup, is notcompatible wit the value to be displayed by the met

Página 31

SECTIONA-1ENA Reference DataSpecifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-1Dimensio

Página 32 - Model 275 HART Communicator

A-2ENRosemount IncNOTEA HART Communicator requires a loop resistance between 250 and 1100 ohms. Do not communicate with the transmitter when power is

Página 33

A-3ENRosemount IncPerformanceThe Model 644 transmitters maintain a specification conformance of at least 3σ.AccuracyTable A-6. Model 644 Input Options

Página 35 - LCD Meter

A-4ENRosemount IncAccuracy ExampleWhen using a Pt 100 (α = 0.00385) sensor input with a 0 to 100 °C span: Digital accuracy would be ±0.15 °C, D/A accu

Página 36

A-5ENRosemount IncAmbient Temperature EffectTransmitters can be installed in locations where the ambient temperature is between –40 and 85 °C (–40 and

Página 37 - A Reference Data

A-6ENRosemount IncTemperature Effects ExampleWhen using a Pt 100 (α = 0.00385) sensor input with a 0–100 °C span at 30 °C ambient temperature:RTDs and

Página 38 - Standard NAMUR-Compliant

A-7ENRosemount IncCE Electromagnetic Compatibility Compliance TestingThe Models 644H and 644R meet all requirements listed under IEC 61326: Amendment

Página 39 - Performance

A-8ENRosemount IncDIMENSIONAL DRAWINGSModel 644R Model 644HShown with Standard CompressionScrew TerminalsShownwithWAGO®SpringClamp Terminals36(1.4)104

Página 40 - Total = ±0.18 °C

A-9ENRosemount IncThreaded-Sensor Universal Head(OptioncodeJ5orJ6)Integral DIN Style SensorConnection HeadShownwithLCDMeter (see note below)Note: A “U

Página 41

A-10ENRosemount IncMountingG-Rail (asymmetric) Top Hat Rail (symmetric)Universal Clip for Mounting toaWalloraRail(part number 03044-4301-0001)Model 64

Página 42 - Frequency Vibration

A-11ENRosemount IncORDERING INFORMATIONTable A-7. Model 644H and Model 644R Ordering Table• =Available— = Not availableModel Product DescriptionHeadMo

Página 43 - Code Options Add

A-12ENRosemount IncDIN Plate Style Temperature Sensor Users (EMEA-Europe, Middle East,and Africa)Remote MountJ5 Universal Head (Junction Box), Aluminu

Página 44 - DIMENSIONAL DRAWINGS

A-13ENRosemount IncCONFIGURATIONStandardUnless specified, the transmitter will be shipped as follows:Table A-9. Standard Configuration ParametersTable

Página 45 - Connection Head

TABLE OF iENCONTENTSTable of ContentsSection 1: IntroductionSafety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 46 - Mounting

A-14ENRosemount IncCustomThe transmitter can be ordered with custom configuration. Use Table A-10 to determine the requirements when specifying the cu

Página 47 - ORDERING INFORMATION

SECTIONB-1ENB Hazardous Locations CertificationsSafety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 48

B-2ENRosemount IncFactory Mutual (FM) ApprovalsE5 Explosion-Proof for Class I, Division 1, Groups B, C, and D. Dust-Ignition Proof for Class II, Divi

Página 49 - Standard

B-3ENRosemount IncCENELEC/KEMA ApprovalsED ATEX Category II 2 G Certification number KEMA 99ATEX8715Flameproof (Zone 1) (Model 644H only)EEx d IIC T6

Página 50

B-4ENRosemount IncSpecial Conditions for Safe Use (X): The transmitter must be installed so that its external terminals and communication pins are pro

Página 51 - SAFETY MESSAGES

B-5ENRosemount IncThe following information is provided as part of the labeling of the transmitter:• Name and address of the manufacturer (Rosemount U

Página 52 - Factory Mutual (FM) Approvals

B-6ENRosemount IncFigure B-3. Canadian Standards Association (CSA) Intrinsic Safety Installation Drawing00644-1064, Rev. AB

Página 53 - CENELEC/KEMA Approvals

B-7ENRosemount IncFigure B-4. Canadian Standards Association (CSA) Explosion-Proof InstallationDrawing 00644-1059, Rev. AC644-1059A01A

Página 54 - Gostandart

B-8ENRosemount IncFigure B-5. Factory Mutual (FM) Intrinsic Safety Installation Drawing 00644-0009,Rev. AA644-0009A01A

Página 55 - INSTALLATION DRAWINGS

B-9ENRosemount IncFigure B-6. Factory Mutual (FM) Explosion-Proof Installation Drawing 00644-1049,Rev. AB

Página 56 - 00644-1064, Rev. AB

iiENRosemount IncSection 4: Hardware and Software Maintenance and TroubleshootingSafety Message . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 58

SECTIONC-1ENC Model 644 and 244E Manual SupplementOld Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Página 59

OLDOLD TRANSMITTERTransmitter DesignSensor Wiring DiagramsModels 644H and 244EH Models 644R and 244ERModels 644 and 244E* Rosemount Inc. provides 4-wi

Página 60

Special Mounting ConsiderationsMounting a Model 644H to a DIN Rail G-Rail Top Hat Rail1. Assemble the appropriate rail clip(part number 00644-5301-000

Página 61 - Supplement

NEWNEW TRANSMITTERTransmitter DesignSensor Wiring DiagramsModels 644H and 244EH Models 644R and 244ERModels 644 and 244E* Rosemount Inc. provides 4-wi

Página 62 - Sensor Wiring Diagrams

C-5ENRosemount IncSpecial Mounting ConsiderationsHART Communicator (Model 644 only)To guarantee proper transmitter functionality and communication, yo

Página 63

C-6ENRosemount IncSPECIFICATIONSOld NewBASEFFA(1)Intrinsically Safe Installation Entity Parameters:PowerLoopUmax:in30 V dc 30 V dcImax:in200 mA 200 mA

Página 64

C-7ENRosemount IncCSA(2)Intrinsically Safe Installation Connection Parameters:Class IDiv. 1GroupsA, B, C,and D• 30 V or less, 330ohms or more• 28 V or

Página 65

C-8ENRosemount Inc

Página 66 - SPECIFICATIONS

SECTION1-1EN1 IntroductionSafety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1Transmitter O

Página 67 - Factory Mutual

1-2ENRosemount IncTRANSMITTER OVERVIEWThank you for choosing the Model 644 Smart Temperature Transmitter. Features of the Model 644 include:• Accepts

Página 68

1-3ENRosemount IncAppendix B: Hazardous Locations Certifications• Hazardous locations certifications• Installation drawingsAppendix C: Model 644 and 2