1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.24/106
7.14 REMOTE PANELS VI620 VI820
The instrument receives up to two remote panels. Using the remote panels provided with the ambient NTC probe the display
measurement, and the control can be managed directly by this probe. Use shielded cable for the connection up to 150mt maximum. In
case of communication failure the upper display shows “noL” (no link).
Use the CAB/CJ30 to interface the ichill connector to the shielded cable.
Remote panel VI620 for models IC260L – IC261L
Remote panel VI820 for models 200 L IC280L – IC281L
8 ANALOG AND DIGITAL OUTPUT CONFIGURATION
8.1 ANALOG INPUT PB1 - PB2 - PB7 - PB8 - PB9 - PB10
Parameters involved:
CF08 = Configuration PB1
CF09 = Configuration PB2
CF14 = Configuration PB7
CF15 = Configuration PB8
CF16 = Configuration PB9
CF17 = Configuration PB10
0. Not enabled
1. Temperature probe PTC for compressor #1 discharge
2. Temperature probe PTC for compressor #2 discharge
3. Temperature probe PTC for compressor #3 discharge
4. Temperature probe PTC for compressor #4 discharge
5. Temperature probe PTC for compressor #5 discharge
6. Temperature probe PTC for compressor #6 discharge
7. Temperature probe NTC for evaporator inlet
8. Temperature probe NTC for evaporator #1 outlet
9. Temperature probe NTC for evaporator #2 outlet
10. Temperature probe NTC for common evaporator outlet
11. Temperature probe NTC for common hot water condenser / recovery inlet
12. Temperature probe NTC for hot water of the condenser / recovery circuit #1 inlet
13. Temperature probe NTC for hot water of the condenser / recovery circuit #2 inlet
14. Temperature probe NTC for hot water of the condenser / recovery circuit #1 outlet
15. Temperature probe NTC for hot water of the condenser / recovery circuit #2 outlet
16. Temperature probe NTC for hot water of the condenser / recovery common outlet
17. Temperature probe NTC for free cooling water inlet circuit
18. Temperature probe NTC for free cooling external air temperature
19. Temperature probe NTC for dynamic setpoint external air / boiler / change over
20. Temperature probe NTC for combined defrost circuit #1
21. Temperature probe NTC for combined defrost circuit #2
22. Temperature probe NTC for auxiliary output #1
Vista de página 23