When the system is running with 100% (eg all the three compressor of a circuit are on) of power and the digital input stop the recovery
function: after the rC04 time delay (minimum on time of the recovery function when activated) and before turning off the recovery valve,
one of the step is turned off for the time set in rC02. When the delay is expired the unit turns off the recovery valve and and the
regulation restarts with its normal running condition.
ATTENTION:
For both the circuits: when the compressor are off because of the thermoregulation and the digital input of the recovery function is
active, the recovery valve is disabled.
39.2 UNIT WITH TWO HYDRAULIC CIRCUIT WORKING IN PARALLEL
FUNCTIONING
Par. rC01 = 2 unit with two circuits working in parallel:
The recovery function from the digital inputs is divided in two steps:
UNIT WITH ONE CIRCUIT RUNNING
If the recovery function is enabled and if the condenser temperature/pressure condition are whithin the limits that circuit starts the
recovery when one of the digital inputs is activated. With active digital input the recovery valve of the circuit is on.
UNIT WITH BOTH THE CIRCUITS RUNNING
If recovery function is enabled, if the condenser temperature/pressure condition are whithin the limits the circuit #1 starts the recovery
(recovery valve #1 on) when the digital input #1 is activated and the circuit #2 starts the recovery (recovery valve #2 on) when the digital
input #2 is activated.
After starting, the recovery function will run at least for the time set in parameter rC04 (minimum time with recovery on).
Between the end of a recovery cycle and the next start the unit waits the time set in Par. rC05 before starting it again.
RECOVERY START–STOP OF THE CIRCUITS 1 AND 2 CONFIGURED WITH ONE STEP EACH
Both for recovery start or stop, the delay time rC02 and rC03 are not counted and the recovery valve is immediately turned on or off.
RECOVERY START OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP
Circuits 1 and 2 configured with more than one step of power (eg each circuit with three compressors), if the thermoregulation requires
to turn on one or more resources and the recovery is activated from the digital input the unit turns on only one step and then waits the
rC02 delay (this delay keep off all the other steps after the recovery is started). After the delay the recovery valve is turned on and, after
the rC03 time (this delay keeps off all the other steps after the recovery is started), the other resources if necessary are turned on.
RECOVERY STOP OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP
Circuits 1 and 2 configured with more than one step of power (eg each circuit with three compressors). After the rC04 time delay
(minimum on time of the recovery function when activated) if the digital input of the recovery is not active the units stops the new
resources for the time set in rC02. After this delay the recovery valve is turned off and the regulation restarts with its normal running
condition.
RECOVERY START OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED
When the system is running with 100% (eg all the three compressor of a circuit are on) of power and the digital input start the recovery
function: before turning on the recovery valve one of the step (depending on the time running hours), is turned off for the time set in
rC02. After rC02 the recovery valve is turned on. Then, after the rC03 time (this delay keeps off all the other steps after the recovery is
started) the resource forced off if necessary is turned on again.
RECOVERY STOP OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED
When the system is running with 100% (eg all the three compressor of a circuit are on) of power and the digital input stop the recovery
function: after the rC04 time delay (minimum on time of the recovery function when activated) and before turning off the recovery valve,
one of the step is turned off for the time set in rC02. When the delay is expired the unit turns off the recovery valve and and the
regulation restarts with its normal running condition.
ATTENTION:
For both the circuits: when the compressor are off because of the thermoregulation and the digital input of the recovery function is
active, the recovery valve is disabled.
40 CONDENSER TEMPERAURE / PRESSURE CONDITION TO ENABLE/DISABLE
THE RECOVERY CYCLE
The recovery can be disabled depending on the condenser condition to avoid a possible high pressure alarm. The function can be
executed by programming the analogue input as condenser transducer 1 or 2 (Par CF07=0 temperature control or CF07= 1 pewssure
control).
FUNCTIONING
40.1 RECOVERY DISABLED
With the recovery function is activated: if the temperature/pressure is equal or higher than the set rC06 (limit of the recovery cycle) the
recovery cycle, of the circuit detected by that transducer, is disabled. When the recovery is disabled the bottom display shows the
following blinking icons: b1rC = for circuit 1, b2rC = for circuit 2.