1592015300 User manual iCHILL 200 L GB r1.3 09/09/2005
Pg.58/106
The regulation is enabled if:
In chiller mode the parameter Sd01 is not equal to 0.
In heat pump mode the parameter Sd02 is not equal to 0.
a 4÷20mA analogue input is configured as dynamic setpoint control or a NTC analogue input is configured as external air
temperature for dynamic setpoint control.
With UP or DOWN keys within the circuit measurement read-out is possible to show the external air temperature indicated by the Et
label.
19.1 DYNAMIC SETPOINT GRAPH
4÷20ma probe configured as dynamic setpoint analogue input:
NTC probe with positive differential:
NTC probe with negative differential: