Emerson ROC364 Manual de Instruções Página 18

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 146
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 17
ROC364 Instruction Manual
2-4 Master Controller Unit, I/O Module Rack, and Wiring Rev Jun/05
The firmware is programmed into flash memory at the factory, but can be reprogrammed in the field.
The application programs are configured by using ROCLINK configuration software including user
programs, such as the Modbus communications protocol.
When used with ROCLINK configuration software, a FlashPAC module can save a configuration to
disk as an .FCF file and later restore these configuration files into a ROC.
The RAM in a FlashPAC can store 87 history points, each holding 35 days of hourly values. Besides
storing history data, the RAM in a FlashPAC stores user program data. The flash ROM portion of the
FlashPAC is programmed with firmware at the factory and can store user programs downloaded through
a communications port.
Table 2-1, ROC Memory Map, on page 2-4 shows how the ROC memory is allocated. Each memory
location range (for example, 00000 to 1FFFF) represents 128 kilobytes of memory.
Determining FlashPAC Version
To determine the version of a FlashPAC, use ROCLINK configuration software. Select ROC >
Information > Other Information > Version Name, which contains the part and version numbers.
NOTE: The version may have been updated by a download of upgrade firmware into the module,
so the label on the actual FlashPAC module might not be accurate.
Table 2-1. ROC Memory Map
Memory Location FlashPAC Usage
00000 to 1FFFF Base RAM Alarm Log, Event Log, and such.
20000 to 3FFFF RAM in FlashPAC History Data Area, part is for scratch-pad memory in FlashPAC
40000 to 5FFFF RAM in FlashPAC History Data Area
60000 to 7FFFF RAM in FlashPAC History Data in FlashPAC
80000 to 81FFF EEPROM (on-board) User Configuration Data
88000 to 9FFFF Flash ROM Operating System and Applications
A0000 to BFFFF RAM in FlashPAC User Program Data in FlashPAC
C0000 to DFFFF Flash ROM User Program Code in FlashPAC
E0000 to FFFFF Flash ROM Operating System Firmware
2.2.3 Diagnostic Inputs and Auxiliary Outputs
The ROC364 MCU monitors the power input voltages, transmitter output voltage, and the board temperature
with diagnostic Analog Inputs designated as “E” points by the configuration software. The inputs can be
calibrated by using ROCLINK configuration software. Two auxiliary Discrete Outputs are also available.
The diagnostic Analog Inputs and auxiliary Discrete Outputs are:
Transmitter supply output voltage – Point Number E1.
Power input voltage – Point Number E2.
Auxiliary Discrete Output #1 – Point Number E3.
Auxiliary Discrete Output #2 – Point Number E4.
MCU board temperature – Point Number E5.