ROC364 Instruction Manual
2-13 Master Controller Unit, I/O Module Rack, and Wiring Rev Jun/05
Table 2-2. MCU LED Indicators
Indicator LED Meaning
On Power is applied to the MCU.
POWER
Off
MCU does not have power. Possible causes are:
Power not present at power terminals.
Power switch is off if so equipped (older units only).
Defective power switch (older units only).
Fuse F1 is open.
Fuse F4 is open.
Polarity reversed.
On Successful startup and the processor is running.
Blinking
Processor is not running and the controller is attempting to restart.
Possible low battery or bad FlashPAC.
SYSTEM
STATUS
Off
If the POWER indicator is on, indicates insufficient voltage is available to power up
the MCU.
On System voltage is present at the AUX PWR OUT 1 terminals.
AUX OUT 1
Off Fuse F2 is open or the output has been disabled by the software.
On System voltage is present at the AUX PWR OUT 2 terminals.
AUX OUT 2
Off Fuse F3 is open or the output has been disabled by the software.
2.5.2 RAM Backup Procedure using ROCLINK Configuration Software
Before removing power to the ROC, perform the following procedure to avoid losing the ROC
configuration and other data stored in RAM.
User programs cannot be saved out of the ROC. Reload user programs from their original disk files as
instructed in the ROCLINK for Windows Configuration Software User Manual (Form A6091) or the
ROCLINK 800 Configuration Software User Manual (Form A6121).
When installing devices in a hazardous area, make sure each device is labeled for use in such
areas. Procedures involving switching power on or off, or procedures for installing or removing
any wiring or components, must be performed only when the area is known to be non-hazardous.
Performance of these procedures in a hazardous area could result in personal injury or property
damage.
To avoid circuit damage when working with the ROC, use appropriate electrostatic discharge
precautions, such as wearing a grounded wrist strap.
1. Save the current configuration data by selecting ROC > Flags > Write to EEPROM or Flash
Memory Save Configuration. This action saves most of the ROC configuration (but not logs or
FST programs) into the permanent memory accessed when a Cold Start is performed.
2. Save the current configuration data to disk by using the Download > Save ROC Configuration
To Disk function. When replacing or upgrading a FlashPAC, the only way to preserve
configuration data is to save the data to disk and then retrieve the information after the FlashPAC
is installed.