Figure 8. Type CSB400 “Series Monitor” Regulator Downstream Control Line Installation
Before installing the regulator, check for
damage which might have occurred in
shipment. Also check for dirt or foreign
matter which may have accumulated in
the regulator body or in the pipeline. Apply
pipe compound to the external threads of
the pipeline and install the regulator so that
ow is in the direction of the arrow cast on
the body. The diaphragm casing assembly
can be rotated to any position relative to the
body. Loosen the two cap screws (key 71,
Figure 11) in order to rotate the diaphragm
casing assembly.
General Installation Instructions
Before installing the regulator,
• Check for damage, which might have occurred
during shipment.
• Check for and remove any dirt or foreign material, which
may have accumulated in the regulator body.
• Blow out any debris, dirt or copper sulfate in the copper
tubing and the pipeline.
• Apply pipe compound to the external threads of the pipe
before installing the regulator.
• Make sure gas ow through the regulator is in the same
direction as the arrow on the body. “Inlet” and “Outlet”
connections are clearly marked.
• Verify that:
- Equipment limits of utilization (PS, TS) corresponds
to the desired operating conditions.
- The inlet is protected by an appropriate device(s) to
avoid exceeding the allowable limits (PS, TS).
• When designing a pressure reducing station using
a CSB regulator, make an analysis if it is necessary
to take into account the effects of wind, snow
and temperature to avoid unnecessary load and
movement to the anges of the equipment.
• If needed, a support may be used under the piping
and regulator/slam-shut body to avoid excessive
pressure force on the regulator/slam shut.
WIDE-OPEN MONITORING REGULATOR PRIMARY WORKING REGULATOR
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
INTERMEDIATE PRESSURE
Type CSB400ET with External Pressure Registration and
Token Relief Wide-Open Upstream Monitor Regulator
INLET PRESSURE
OUTLET PRESSURE
UPSTREAM
BLOCK VALVE
DOWNSTREAM
BLOCK VALVE
MINIMUM OF 4 X OUTLET
PIPING DIAMETER