CSB400 Series
14
Installation Location
The installed regulator should be adequately
protected from vehicular trafc and damage from
other external sources.
Install the regulator with the vent pointed vertically
down, see Figures 7 through 10. If the vent cannot
be installed in a vertically down position, the regulator
must be installed under a separate protective cover.
Installing the regulator with the vent down allows
condensation to drain, minimizes the entry of water
or other debris from entering the vent, and minimizes
vent blockage from freezing precipitation.
Do not install the regulator in a location where there
can be excessive water accumulation or ice formation,
such as directly beneath a downspout, gutter or roof
line of building. Even a protective hood may not
provide adequate protection in these instances.
Install the regulator so that any gas discharge
through the vent or vent assembly is over 0.91 m /
3 feet away from any building opening.
Regulators Subjected to Heavy
Snow Conditions
Some installations, such as in areas with heavy snowfall,
may require a hood or enclosure to protect the regulator
from snow load and vent freeze over.
Downstream Control Line Installation
!
WARNING
Failure to install a downstream control
line could result in a hazardous condition.
Install downstream control line(s) to the
slam-shut device when construction uses
external pressure registration.
The regulator and slam-shut device
will not control pressure or shutoff if a
downstream control line is not installed
on those constructions where external
pressure registration is required.
CSB400 Series regulators with an “ET” or “EN” in the
type number use external pressure registration. To
communicate the downstream pressure to the regulator,
connect a downstream control line tubing to the 3/4 NPT
control line tapping in the lower diaphragm casing and
connect the other end of the tubing downstream of the
regulator outlet with a minimum distance of 4 times the
outlet pipe diameter.
For Types CSB400 and CSB404 with external control
lines, use tubing with an outer diameter of 9.5 mm /
0.375 inch or larger. For Types CSB420, CSB424,
CSB450 and CSB454 with external control lines, use
tubing with an outer diameter of 13 mm / 0.5 inch or larger.
The Types CSB410, CSB414, CSB430 and CSB434
are dedicated wide-open monitoring regulators and are
installed upstream of a primary working regulator. Refer
to Figure 8 for installation of the downstream control
line. To communicate the downstream pressure to the
wide-open monitor regulator, connect a downstream
control line tubing to the 3/4 NPT control line tapping in
the lower diaphragm casing of the monitor regulator and
connect the other end of the tubing downstream of the
regulator outlet with a minimum distance of 4 times the
outlet pipe diameter.
For Types CSB410 and CSB414, use tubing with an
outer diameter of 9.5 mm / 0.375 inch or larger.
For Types CSB430 and CSB434, use tubing with an
outer diameter of 13 mm / 0.5 inch or larger.
Downstream Control Line Installation with
Integral True-Monitor™
Refer to Figure 9. When installing the Types CSB403
and CSB423 regulators, connect downstream control
line tubing to the lower casing of the primary regulator,
and run the tubing downstream of the regulator outlet
with a minimum distance of 4 times the outlet pipe
diameter. Connect a second, separate downstream
control line tubing to the lower casing of the Integral
True-Monitor, and run the tubing downstream of the
regulator outlet with a minimum distance of 4 times the
outlet pipe diameter.
For Type CSB403 with external control lines, use tubing
with an outer diameter of 9.5 mm / 0.375 inch or larger
for both the primary regulator and Integral True-Monitor.