15
Reference Manual
00809-0100-4803, Rev DA
Section 4: Operation and Maintenance
April 2013
Operation and Maintenance
Figure 4-3. Calibration - static pressure calibration tab
Zero trim and lower sensor trim
The type of static pressure sensor equipped in the transmitter can be determined by referring to
the Static Pressure Sensor Type heading. This determines whether a zero trim (gage sensor) or
lower sensor trim (absolute sensor) required to correct for mounting position effects.
To perform a zero trim on a gage static pressure sensor, click on the Zero Trim button under the
Static Pressure Sensor Trim heading and follow the on-screen prompts. The transmitter must be
within five percent or less of the maximum span of true zero (zero-based) in order to calibrate
with zero trim function.
To correct for mounting position effects on transmitters equipped with an absolute static
pressure sensor, perform a lower sensor trim. This is accomplished by clicking on the Lower
Sensor Trim button and following the on-screen prompts. The lower sensor trim function
provides an offset correction similar to the zero trim function, but it does not require a
zero-based input.
Upper and lower sensor trim
To perform a Static Pressure Full Sensor Trim, first click on the Lower Sensor Trim button and
follow the on-screen prompts. Next, click on the Upper Sensor Trim button and follow the
on-screen prompts.
Note
It is possible to degrade the performance of the transmitter if the full sensor trim is done
improperly or with inaccurate calibration equipment. Use a pressure input source that is at least
three times more accurate than the transmitter and allow the pressure input to stabilize for ten
seconds before entering any values.