Reference Manual
00809-0100-4803, Rev DA
Appendix B: Product Certifications
April 2013
Product Certifications
B.4.1 Hazardous Locations Certifications
North American certifications
FM approvals
E5 Explosion-proof for Class I, Division 1, Groups B, C, and D; dust-ignition proof for Class II
and Class III, Division 1, Groups E, F, and G; hazardous locations; enclosure Type 4X,
conduit seal not required.
I5 Intrinsically Safe for use in Class I, Division 1, Groups A, B, C, and D; Class II, Division 1,
Groups E, F, and G; Class III, Division 1; Class I, Zone 0 AEx ia IIC when connected in
accordance with Rosemount drawing 03151-1206; Non-incendive for Class I, Division 2,
Groups A, B, C, and D Enclosure Type 4X
For entity parameters see control drawing 03151-1206.
Canadian Standards Association (CSA)
All CSA hazardous approved transmitters are certified per ANSI/ISA 12.27.01-2003.
E6 Explosion-proof for Class I, Division 1, Groups B, C, and D; Dust-Ignition-Proof for Class II
and Class III, Division 1, Groups E, F, and G; suitable for Class I, Division 2, Groups A, B, C,
and D, CSA Enclosure Type 4X; conduit seal not required.
I6 Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D when connected in
accordance with Rosemount drawings 03151-1207;
For entity parameters see control drawing 03151-1207.
European certifications
I1 ATEX Intrinsic Safety
Certificate No.: 08ATEX0064X II 1G
Ex ia IIC T4 (T
a
= -60 °C to 70 °C) -HART
1180
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V test as defined in Clause 6.3.12 of EN
60079-11. This must be considered during installation.
N1 ATEX Type n
Certificate No.: Baseefa 08ATEX0065X II 3 G
Ex nA nL IIC T4 (T
a
= -40 °C TO 70 °C)
U
i
= 45 Vdc max
IP66
Special conditions for safe use (x)
The apparatus is not capable of withstanding the 500 V insulation test required by Clause 6.8.1 of
EN 60079-15. This must be taken into account when installing the apparatus.
Table B-1. Input parameters
Loop / Power Groups
U
i
= 30 V HART
I
i
= 300 mA HART
P
i
= 1.0 W HART
C
i
= 14.8 nF HART
L
i
= 0 HART