Product Data Sheet
00813-0100-4811, Rev DA
Catalog 2008 - 2009
Rosemount 3300 Series
Level-18
National Supervision and Inspection Center for
Explosion Protection and Safety of Instrumentation
(NEPSI) Approvals
E3 Flameproof: GYJ071096
Ex dia IIC T6 (-20°C<T
a
<+60°C). DIP A21 T
A
T6 IP66
U
m
=250 V
Approval valid for HART
®
option.
I3 Intrinsically Safe: GYJ06459X, GYJ06460X
Ex ia IIC T4 (-20°C<T
a
<+60°C).
U
i
=30 V dc, I
i
=130 mA, P
i
=1.0 W, C
i
=0 nF, L
i
=0 H.
Approval valid for HART
®
option.
Technology Institution of Industrial Safety (TIIS)
Approval
E4 Flameproof:
Transmitter: Ex d [ia] IIB T6 (-20°C<T
a
<+60°C)
Probe: Ex ia IIB T6
Approval valid for HART
®
option.
IECEx Approval
E7 Flameproof:
Ex d [ia] IIC T6 (T
amb
= -20°C + 60°C) IP66
IECEx TSA 04.0013X
Approval valid for HART
®
option.
SPECIAL CONDITIONS FOR SAFE USE (X)
The apparatus metallic enclosure must be electrically bonded to
earth. The conductor used for the connection shall be equivalent
to a copper conductor of 4 mm
2
minimum cross-sectional area.
Where it is required that an unused conduit entry is to be closed by
means of the blanking plug, the plug supplied by the equipment
manufacturer with this equipment is certified for this purpose under
this certification.
Maximum Voltage U
m
= 250 V.
I7 Intrinsic Safety:
Ex ia IIC T4 (T
a
= 60°C) IP66
IECEx TSA 04.0006X
U
i
= 30 V, I
i
= 130 mA, P
i
= 1 W, C
i
= 0 nF, L
i
= 0 mH
Approval valid for HART
®
option.
SPECIAL CONDITIONS FOR SAFE USE (X)
The programming port must not be used in the hazardous area.
The apparatus metallic enclosure must be electrically bonded to
the earth. The conductor used for the connection shall be
equivalent to a copper conductor of 4 mm
2
minimum
cross-sectional area.
The input parameters stated above must be taken into
consideration during the installation of the apparatus.
Combination Approvals
KA ATEX and CSA Flameproof / Explosion Proof
KB FM and CSA Explosion Proof
KC ATEX and FM Flameproof / Explosion Proof
KD ATEX and CSA Intrinsic Safety
KE FM and CSA Intrinsic Safety
KF ATEX and FM Intrinsic Safety
Approval valid for HART
®
option.
For information on hazardous locations installations,
refer to the Reference Manual.