Technical Information
D7.21.2/1011/E
16/17
Flash
code
Alarm conditions
Possible failure reasons
Troubleshooting measures
4
Connection lost
CT to sensor
Warning: Appears when the signal
from current sensor is not
communicated to the sensor module.
The current sensor is not
connected to the sensor module.
Faulty current sensor.
Faulty sensor module.
Verify if the CT connector is connected to the sensor module. If not connect the 4-pin
current sensor connector into the sensor module.
Verify if there is continuity between pin 3 & 4 (closest to the latch) of the current
sensing connector. The resistance should be less than 1 . If the resistance is
greater than 1 , replace the current sensing module. Be certain that the receptacles
are fully engaged in the connector block.
Verify if the Amp and Volts values are correctly displayed. If not, inspect the wire
harness connector to ensure that the pins are fully engaged.
If the above-mentioned trouble shooting measures didn't give the positive results, the
reason is faulty sensor module or mis-installed connector. Replace the faulty sensor
module with new one.
5
Communication
Error
Warning: Appears when there is no
communication between control
module and sensor module or rack
controller
Communication between
CoreSense control module and
rack controller has been lost.
Communication between the
CoreSense control module and
the sensor module has been lost.
Is there a communication network? If not, set the network dip-switch to "stand-alone"
and press reset.
Is there a communication network? If not, verify that the communication harness is
engaged at both the CoreSense module and the sensor module.
If the LED on the top edge of the sensor module is dark, verify 24VAC power to the
sensor module, or replace the sensor module.
If communication network amber light is continuously on, reverse the communication
wire polarity. If voltage between centre pin and the right or left pin isn't 2.3-2.6VDC,
inspect for communication wire failure or wire strands that are "shorting" between the
wires or to ground.
6
Locked rotor
Trip: Appears when the excessive
current is present in the compressor.
Refer AE bulletin for more details.
Lockout: Appears when 10
consecutive locked rotor trip alarms
occur.
Motor rotor is mechanically seized.
Excessive current present in the
compressor.
Damaged valve plates in cylinder
head.
Verify that motor voltage is adequate (+/- 10% of nominal rated voltage), especially
during the starting event.
Start compressor with no load. If it does start with no load, inspect the valve plate(s)
for damage or look for other causes of leak-back.
7
Missing phase
Trip: Appears when there is a missing
phase / single phasing.
Lockout: Appears when 10
consecutive missing phase trip
alarms occur.
Loose wiring connections at the
terminals inside compressor T-Box.
Worn out contactors.
Line break in one of the phases.
Verify voltage supply from the main power buss.
Verify voltage into and out of contactor (Repair or replace contactor if necessary).
Verify that motor electrical connections are tight at the compressor motor terminals.