Technical Information
D7.21.2/1011/E
7/17
3.13 Alarm history and running conditions
Operating information
Alarm history
Number of compressor running hours -
8 days alarm history
Accumulated running time without good oil
pressure
Most recent 10 alarms
Number of switching cycles
Total number of alarms since the compressor first
operation
Compressor power consumption*
Current, voltage, power factor*
*This data is not stored in CoreSense EEPROM memory. These values can be stored in a laptop using CoreSense PC
Interface Software or Modbus
®
communication.
Table 3
3.14 Compressor status codes
Steady green: An indication of normal operation. There are no faults or issues with the compressor.
Flashing green: An indication that there is an alert (warning) condition. The compressor can still be
running.
Flashing orange: An indication that the compressor has tripped with auto reset.
Flashing red: An indication that the compressor is in lockout state.
Solid red: An indication that the control module has failed.
3.15 LEDs on the module to display the failure alarms
For warning/alert (green), trip and lockout (red), the flash count is defined as 0.1 second „on‟ and 0.4 second „off‟
with a 2-second pause before the flash count repeats (timings are +/- 50 ms).
Definitions:
Trip: The module has shut off the compressor due to a fault condition. The compressor will be available to
run when the fault condition no longer exists, and the minimum off time has been satisfied.
Lockout: The module has shut off the compressor due to a fault condition. The compressor will be
available to run again when the fault condition has been cleared and manual or remote reset is done.
Figure 4
Alert alarms
Compressor will not turn off.
Trip alarms
Compressor turns off for some
time with automatic reset.
Lockout alarms
Compressor turns off.
Manual reset necessary.