D7.21.2/1011/E
8/17
Status LED troubleshooting information
Without
sufficient oil
pressure for 2
minutes
If flashing green, compressor has been
without sufficient oil pressure for 4 seconds.
If flashing red, compressor has been
without sufficient oil pressure for 2 minutes.
If flashing orange, compressor is turned
off because motor temperature has
exceeded set point. (3 series PTCs; 1 input)
(Trips at 4.5K Ohms, and will reset when
below 2.75K Ohms.)
Exceeds max
set point
(configured in
EEPROM from
iPRO)
If flashing green, the discharge
temperature probe is open or disconnected.
If flashing orange, discharge temperature
has exceeded set point; compressor is
turned off for 2 minutes before resetting.
If flashing red, discharge temperature has
exceeded set point and the compressor is
locked out.
(The customer has configured the module
to lock out when the DLT temperature
exceeds the maximum set point.) DLT
probe is FACTORY INSTALLED
If flashing green, current sensor is
disconnected from the module. Compressor
run state is not known by module.
Communication between Control module
and iPro (/System) Controller has been lost.
Communication between Control module
and Sensor module has been lost.
Configuration miss-match between SW
configuration from iPro and HW (network
mode)
If flashing orange, compressor failed to
start, and excessive current may be present
in the compressor. The compressor is
turned off and will remain off for 5 minutes.
If flashing red, compressor failed to start,
and excessive current may be present in
the compressor. The compressor is locked
out after 10 consecutive events.
If flashing orange, compressor is turned
off due to missing phase.
If flashing red, the compressor is locked out
after 10 consecutive missing phase alarms.
If flashing orange, compressor is turned
off due to low compressor voltage.
If flashing red, the compressor is locked
out after 10 consecutive low voltage alarms.
If flashing orange, compressor is turned
off due to voltage imbalance.
If flashing red, the compressor is locked
out after 10 consecutive voltage imbalance.
Table 4