Type LR128
6
Note
The Type LR128 internal inlet strainer
is intended to prevent occasional
large particles from entering the main
valve. If the owing media contains
continuous particles, upstream ltration
is recommended before the main valve
and in the pilot supply piping (reference
Figure 3). See the Specications section
for the corresponding mesh size of the
internal inlet strainer.
2. A Type LR128 relief valve or backpressure regulator
may be installed in any orientation, as long as ow
through the unit matches the direction of the arrow
on the main valve body and the pilot vent is pointed
down. However, for easier maintenance, install the
regulator with the bonnet up.
CAUTION
Provide adequate support to the bonnet
when disassembling Type LR128
relief valve or backpressure regulator
installed in a vertical installation or
other application where the bonnet is
not oriented upward. Without adequate
support, the bonnet may fall and cause
physical injury when the cap screws
are loosened.
3. The standard pilot mounting position is as shown
in Figure 1. Rotate the bonnet (key 2, Figure 7) or
the pilot (Figure 14) for other mounting positions.
4. An upstream control line is required and must be
installed – as shown in Figure 3 – into the 1/8 NPT
connection in the pilot body assembly (Figure 14).
Do not make the upstream pipeline connection in
or directly downstream of a turbulent area such
as a swage or elbow. A lter or strainer may be
installed in the control line upstream of the pilot
to provide clean uid. Inspect and clean this lter
regularly to make sure it is not plugged, which can
prevent proper pilot operation.
5. Run a supply pressure line from the upstream
pipeline to the restrictor inlet (use 3/8 NPT outer
diameter tubing or larger). Install a lter or strainer
upstream of the restrictor, if needed, to keep the
supply source from clogging the restrictor or pilot.
Inspect and clean this lter regularly to make sure
it has not been plugged which can prevent proper
relief valve or backpressure operation.
6. Apply a good grade of pipe compound to the
external pipeline threads for a threaded body
or use suitable line gaskets for a anged body.
Use approved piping procedures when installing
the relief valve or backpressure regulator.
!
WARNING
When used in relief valve service, the
Type LR128
may leak toxic chemical to
the environment. In toxic or hazardous
liquid service, leaked chemical may
accumulate and cause personal injury,
death or property damage due to
escaping uid.
To prevent such injury or damage,
provide piping or tubing to vent the
hazardous liquid to a remote, safe
location away from air intakes or any
hazard-prone location.
The exhaust
piping must be designed and installed to
guard against excessive ow restriction.
Protect the vent line or stack opening
against condensation or clogging.
For safety during shutdown, vent valves
are required immediately upstream
and downstream of the main valve on a
backpressure or bypass installation.
7. If system operation during maintenance is required,
install isolating and vent valves as needed.
8 The pilot spring case vent (key 54, Figure 14) must
be kept open to atmospheric pressure. A clogged
pilot spring case vent may cause the relief valve
or backpressure regulator to function improperly.
To prevent plugging (and to keep the spring case
from collecting moisture, corrosive chemicals or
other foreign material) point the vent down, orient
it to the lowest possible point on the spring case
or otherwise protect it. Protect the vent assembly
from icing, moisture or debris that may cause
blockage, as required. Inspect the vent regularly
to make sure it has not been plugged. To change
the vent orientation, twist the vent assembly in the
spring case.
9. To remotely vent a spring case, remove the vent
and install obstruction-free tubing or piping into
the 1/4 NPT vent tapping. Provide protection on a
remote vent by installing a screened vent cap onto
the remote end of the vent pipe.