RELIEF PRESSURE CONTROL
BACKPRESSURE CONTROL
Figure 3. Typical Type LR128 Installation Schematic
A - VENT (TO DOWNSTREAM PIPING)
C - TO TYPE LR128 LOADING CHAMBER
D - PILOT SUPPLY (FROM UPSTREAM)
Startup and Shutdown
CAUTION
If pressure is introduced rst to the
main valve before the pilot, the main
valve may go wide-open and subject the
downstream system to full inlet pressure.
Note
The maximum inlet pressure for specic
constructions are given in Tables 1 and
2. Use a pressure gauge to monitor inlet
pressure during startup.
Relief Installation (Figure 3)
Startup
1. Close upstream vent valve (not shown).
2. Slowly open block valve and hand valve, if installed.
3. Adjust the pilot as needed.
Shutdown
1. Close block valve and hand valve, if installed.
2. Slowly open upstream vent valve (not shown).
Backpressure Installation (Figure 3)
Startup
1. Close upstream and downstream vent valves
(not shown).
2. Slowly open upstream block valve rst and then
slowly open downstream block valve.
3. Adjust the pilot as needed. If the pilot is not piped
downstream, make sure the pilot exhaust is
pointed in the correct direction.
Shutdown
1. Close upstream block valve rst and then close the
downstream block valve.
2. Open downstream and upstream vent valves
(not shown).
BLOCK VALVE STRAINER BLOCK VALVE
TYPE MR98H
TYPE LR128
MAIN VALVE
TYPE 112 RESTRICTOR
A
C
D
ALTERNATE PILOT
EXHAUST PIPING
NON-RESTRICTIVE
VENTS AND PIPING
ALTERNATE PILOT
EXHAUST PIPING
TYPE MR98H PILOT
TYPE LR128
MAIN VALVE
TYPE 112 RESTRICTOR
D
C
A
CONTROL LINE
ALTERNATE CONTROL LINE
STRAINER
HAND VALVE
STRAINER
BLOCK VALVE
MAIN PRESSURE LINE