Type LR128
9
W4559_1
RESTRICTOR ADJUSTMENT
Figure 5. Restrictor Adjustment and Restrictor Setting Guide
RESTRICTOR SETTING GUIDE
TYPE 112 RESTRICTOR ADJUSTMENT GUIDE
(1)
Regulator Performance 2 4 6 8
Accuracy
Hysteresis
Stability
Speed of Response (Main Valve Closing)
Speed of Response (Main Valve Opening)
Increased performance
Decreased performance
1. See Table 4 for recommended restriction settings.
Table 4. Recommended Setting for Type 112 Restrictor
BODY SIZE
RECOMMENDED RESTRICTION SETTING
In. DN
1 and 2 25 and 50 “6” (other restriction settings may be used)
3 80 “6” or “8” (lower settings are not recommended)
4 100 “8” (lower settings are not recommended)
The frequency of inspection and parts replacement
depends upon the severity of service conditions,
applicable codes and government regulations and
company inspection procedures. Table 8 lists possible
relief valve or backpressure regulator issues and
solutions for them.
Type LR128 Main Valve Trim
Parts Maintenance
Instructions are given for complete disassembly and
assembly. The main valve may remain in the pipeline
during maintenance procedures. Key numbers are
referenced in Figures 7 through 11.
!
WARNING
Avoid personal injury or damage
to property from sudden release of
pressure or uncontrolled process
uid. Before starting to disassemble,
carefully release all pressures
according to the Shutdown procedure.
Use gauges to monitor inlet, loading
and outlet pressures while releasing
these pressures.