Instruction Manual
D103621X012
4320 Position Monitor
April 2014
10
Installing Standard and Extended Life Power Modules
There are two battery-sourced power options, standard life and extended life power modules. Refer to the power
module warning labels, shown in figure 4, to determine which power module you have. Refer to figure 5 when
installing.
Figure 4. Warning Labels from Power Module
STANDARD LIFE POWER MODULE
EXTENDED LIFE POWER MODULE
GE57654X012
GE57655X012
Note
Default configuration is for a standard power module. If installing the extended life power module you must change the
configuration. Incorrect power module configuration will affect remaining days of life calculations. If using the Field
Communicator go to Configure, Manual Setup, Power Module, Reset Module Data. In AMS Device Manager go to Configure, Manual
Setup and select Reset Power Module Variables from the Power tab.
To install the power module:
1. Loosen the two instrument screws and open the cover.
2. Align the power module over the four banana plug connectors and insert on the main board.
3. Insert the four self tapping screws into the corresponding female receptors on the cover/main board assembly and
tighten to a torque of 0.282 N•m (2.5 lbf•in) to ensure that the power module is secured properly.
4. If you are replacing the power module see the additional steps to reset the power module remaining life counter, in
the Resetting Power Module Variables procedure found on page 63.
5. Close the cover and tighten the instrument cover screws to a torque of 5.6 to 6.7 N•m (50 to 60 lbf•in).