Emerson Fisher 4320 Manual de Instruções Página 44

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 43
Instruction Manual
D103621X012
4320 Position Monitor
April 2014
44
Reset Accumulated Count —select Yes to reset the accumulated count to 0 (zero). This is typically done when
maintenance to valve and/or actuator has been performed. Select No to retain the current cycle count.
Enable Cycle Count Alert
Cycle Trip Point—used to adjust the trip point.
DSwitch State Alerts—select the switch state monitors that report their outputs as status alerts.
Switch Latched—condition of the optional latch for the switch state variable.
Opened/High Limit Tripped—indicates the input signal meets the user-specified requirements for the opened or high
limit.
Closed/Low Limit Tripped—indicates the input signal meets the user-specified requirements for the closed or low limit.
Enable 'Latched' Alert—enables the alert reporting that the switch state is latched. If latching mode is active, this alert
must be enabled.
Enable 'Opened/High' Alert—enables the alert reporting that the valve is opened, or the PV is above the high trip point.
Enable 'Closed/Low' Alert—enables the alert reporting that the valve is closed, or the PV is below the low trip point.
DSwitch Response Alerts
Note
Switch Response alerts are not available in snap-acting mode.
Transition Alert—when enabled indicates the process state is in transition (i.e. between limits).
Transition Dwell Alert—when enabled indicates that the input signal has been in the transition state for longer than the
specified time window.
Transition Dwell—indicates the length of time in the current state.
Enable 'In Transition'—enables the alert reporting that the position signal is between trip points.
Enable 'Transition Dwell'—enables the alert reporting that the output has spent excessive time between trip points.
Transition Dwell Threshold—indicates the length of time the monitored signal must remain in the transition state before
the Transition Dwell alert is set.
DController Alerts (On/Off Control)
Note
Controller Alerts are disabled by default.