Instruction Manual
D103621X012
4320 Position Monitor
April 2014
5
Table 1. Specifications
Available Mountings
J Quarter‐turn rotary‐shaft
J sliding‐stem or
J linear applications
Can also be mounted on other actuators that comply
with IEC 60534‐6‐1, IEC 60534‐6‐2, VDI/VDE 3845
and NAMUR mounting standards
Input Measurement
Stem Travel (linear movement)
Minimum: 2.5 mm (0.10 inch)
Maximum: 210 mm (8.25 inches)
Shaft Rotation (rotary movement)
Minimum: 45_
Maximum: 90_
Shaft Rotation (rotary movement, arced array)
Minimum: 13_
Maximum: 30_
Measurement Output
Analog: 0-100%
Discrete: on/off switches (2)
Reference Accuracy
1% of span
On/Off Control
Output Signal
Pneumatic signal as required by the actuator, up to
95% of supply pressure
Minimum Span: 3.1 bar (45 psig)
Maximum Span: 7 bar (101 psig)
Action: Single or Double Acting
Supply Pressure
Minimum: 3.1 bar (45 psig)
Maximum: 7 bar (101 psig)
Supply Medium
Air or Natural Gas
Air: Supply pressure must be clean, dry air that
meets the requirements of ISA Standard 7.0.01. The
supply air at the device should have a dew point less
than -20_C (-4_F).
Natural Gas: Natural gas must be clean, dry, oil-free
and noncorrosive. H
2
S content should not exceed
20 ppm. Refer to ATEX and IECEx Special Conditions
of Safe Use on page 16 for additional information on
use of natural gas as supply medium.
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized.
Air Consumption
(1)
4320
At 5.5 bar (80 psig) supply pressure:
0.036 m
3
/hr (1.27 scfh)
Pilot Valve Leakage
Maximum at 20_C: 8 ml/min (0.0003 scfm/min)
Maximum at -20_C: 800 ml/min (0.028 scfm/min)
Air Capacity / Flow Rate
Supply Pressure: 1.2 Cv
Connections (Optional)
Supply, Output Pressure, and Vent: 1/4 NPT
Wireless Set Point Command
IEC 62591 (WirelessHART) 2.4 GHz DSSS
Local User Interface
Liquid Crystal Display (LCD)
Two pushbuttons for navigation, setup, and
calibration
Communication Protocol
HART 7
Maintenance Port Communication Signal
Bell 202 Voltage Signaling: 1200 bps binary
phase-continuous Frequency-Shift-Keying (1220 Hz
mark, 2400 Hz space) superimposed on voltage level
Initial Dynamic Variable Assignments (Default)
Dynamic
Variable
Assignment
DEVICE STRUCTURE
Control Snap Control Monitor
Primary (PV) Position Position Position
Secondary (SV) Set Point Set Point Switch States
Tertiary (TV) Switch States Switch States Cycle Counter
Quaternary (QV) Supply Voltage Supply Voltage Supply Voltage
Refer to table 4 for a complete list of Device Variables
Wireless Communication Signal
2.4 GHz, DSSS, WirelessHART
Maximum 10 dBm (10 mW) EIRP at 2.46 GHz
‐continued‐