
Instruction Manual
D103621X012
4320 Position Monitor
April 2014
15
Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring
requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may
override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product.
Always refer to the nameplate itself to identify the appropriate certification. Contact your Emerson Process Management sales
office for approval/certification information not listed here.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion,
and area re‐classification.
CSA (C/US)
Intrinsically Safe
Monitor Version
Battery Sourced Power Module w/out Pneumatic Output External Power w/out Pneumatic Output
Ex ia Intrinsically Safe Ex ia Intrinsically Safe
Class I, Division 1 GP ABCD T3/T4/T5 Class I, Division 1 GP ABCD T5(Tamb ≤ 80_C)
Ex ia IIC T3/T4/T5 Ex ia IIC T5 (Tamb ≤ 80_C)
Class I Zone 0 AEx ia IIC T3/T4/T5 Ga Class I Zone 0 AEx ia IIC T5(Tamb ≤ 80_C) Ga
Install per control drawing GE59530 as shown Install per control drawing GE59530 as shown
in figure 8 and 9 in figure 8 and 10
Enclosure: Type 4X, IP66 & IP67 Enclosure: Type 4X, IP66 & IP67
T3(Tamb ≤ 85_C), T4(Tamb ≤ 75_C), T5(Tamb ≤ 40_C) Temperature Range: -40_C to 80_C
Temperature Range: -40_C to 85_C
Control Version
Battery Sourced Power Module with Pneumatic Output External Power with Pneumatic Output
Ex ia Intrinsically Safe Ex ia Intrinsically Safe
Class I, Division 1 GP ABCD T4/T5/T6 Class I, Division 1 GP ABCD T5
Ex ia IIC T4/T5/T6 Ex ia IIC T5
Class I Zone 0 AEx ia IIC T4/T5/T6 Ga Class I Zone 0 AEx ia IIC T5 Ga
Install per control drawing GE59530 as shown Install per control drawing GE59530 as shown
in figure 8 and 9 in figure 8 and 10
Enclosure: Type 4X, IP66 & IP67 Enclosure: Type 4X, IP66 & IP67
T4(Tamb ≤ 50_C), T5(Tamb ≤ 46_C), T6(Tamb ≤ 31_C) T5(Tamb ≤ 50_C)
Temperature Range: -20_C to 50_C Temperature Range: -20_C to 50_C
Comentários a estes Manuais