Emerson Fisher 4320 Manual de Instruções Página 11

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 10
Instruction Manual
D103621X012
4320 Position Monitor
April 2014
11
X0552
POWER
MODULE
HART
TERMINALS
BANANA PLUG CONNECTORS (4)
SELF TAPPING SCREWS (4)
GND
TERMINAL
PWR TERMINAL
COVER SCREWS
Figure 5. Fisher 4320 Wireless Position Monitor with Battery Sourced Power Modules
FILTER (2)
Installing Unit Supplied with External Power Option
Refer to figure 6 when installing the wiring.
1. Loosen the two instrument screws and open the cover.
WARNING
Select a cable gland that is rated for the environment of use (such as hazardous area, ingress protection and temperature).
Failure to use properly rated cable glands can result in personal injury or property damage from fire or explosion.
When installing the cable gland or conduit fitting minimize the amount of wires remaining in the housing cavity so they do
not get compressed or damaged when closing the cover in step 7.
2. Insert a user-supplied cable gland or conduit fitting into the housing.
3. Insert the wires through the cable gland/conduit fitting.
4. Connect the wires to the connections as shown in figure 6. The terminals and electronics connections are
polarity-insensitive; ie., you can connect the positive or negative wire to either terminal screw.
5. As shown in figure 6, a ground terminal is available for connecting a safety ground. Make connections to this
terminal following national and local codes and plant standards.
6. Tighten the wiring terminal screws.
7. Close the cover and tighten the instrument cover screws to a torque of 5.6 to 6.7 N•m (50 to 60 lbf•in).