10
Grommets are included to minimize the chance of
chaffing where the cable passes through sheet metal
openings.
Refer to figure 2.11 for details regarding the commu-
nication board jumper positions.
Important! Note that RS485 is polarity sensitive.
“Pos” wires must connect to other “Pos” terminals,
and “Neg” wires must connect to other “Neg” termi-
nals. The shield wire is connected to the center
terminal, or “0 volt” position. Refer to section 4.4.12
for voltage specifications.
Figure 2.10 Intelligent Store™ Discus®
Communications Board
Figure 2.11 Communications Wiring and Jumper
Position
2.5.1 Wiring Types
A shielded, twisted pair cable such as Belden #8641
(24 AWG) or Belden #8761 (22AWG) should be used
for the communication wiring.
2.6 Intelligent Store™ Discus® Service
Manual
Refer to sections 3, 4, and 5 of this document for
detailed commissioning, service and troubleshooting
instructions.
2.7 Compatibility of Service Compressors
The following S/Ns may be used to determine
whether service compressors are compatible with
Intelligent Store™ Discus® hardware and acces-
sories.
2D built on or after S/N 04D
3D built on or after S/N 04D
4D built on or after S/N 05D
2.8 Intelligent Store™ Discus® Model
Numbers
2D, 3D, and 4D Discus® compressors with a -600
series S/E (the last 3 digits of the model) are
equipped from the factory with Intelligent Store™
Discus® hardware and accessories.
Figure 2.12 Intelligent Store™ Discus® Model
Number
The number defines service valve configuration as
well as accessory content such as crankcase heaters,
liquid injection and modulation.
RS485 Connector in Intelligent
Store™ Discus® Front Box
Jumpers (3) for
Termination Definition