compressor has been off for several
seconds will not activate this code.
9 Module Supply Voltage Trip - If the module
supply voltage drops below 170 volts for 2
seconds, the compressor is shut down to
prevent contactor chatter. When the con-
trol voltage rises above 180 volts for 2 sec-
onds, the module will enable the compres-
sor to run again.
The “Module Power” voltage is used to
make this determination.
A Compressor Module Failure Lockout - An
internal module fault has been detected
and communication with the rack con-
troller is not possible. To reset, shut off the
module power for 5 seconds or more - a
successful restart may or may not occur.
Remote resetting is possible if controller
communications still exist.
b Discharge Pressure Trip - The discharge
pressure has exceeded the setting of the
high pressure cutout switch (360 psi). The
module will enable the compressor to run
when the head pressure drops below the
switch reset level (250 psi).
The module senses the voltage drop
across the pressure switch to deter-
mine whether the high discharge pres-
sure cutout switch is open. The high
discharge pressure switch is in series
with the pilot circuit
C Discharge Temperature Lockout - The
peak internal temperature has exceeded
the limit of 310º F. Manual reset or remote
reset is required to enable the compressor
to run again.
The temperature probe in the head is
used to monitor the discharge tempera-
ture.
d Loss of Communication Mode - If commu-
nication is lost for 5 minutes or more, this
code will flash. The compressor will run in
stand-alone mode (“off” or “on” depending
on how the E2 “failsafe” has been
programmed). Normal operation will
resume when communications have been
re-established.
A blinking decimal at the LED indicates
that communication between the mod-
ule and the Einstein™ is taking place.
E Disabled by Rack Controller - The com-
pressor is disabled until the module stops
receiving this command from the rack con-
troller.
F Phase Loss Trip / Lockout - One phase of
the compressor power is missing at start-
up or during running. The compressor will
shut down for a 5 minute period before it is
enabled to run again. If there are 10 con-
secutive trips, the compressor is locked
out. Manual reset, remote reset or remov-
ing module power for 5 seconds is
required to enable the compressor to run
again.
The module monitors the voltage at the
three terminal plate connections.
L No 3-Phase Compressor Power Trip -
None of the 3-phases of compressor
power were delivered to the compressor
when the module issued a command for
the compressor to run.
The compressor will run when power is
available if a run command is still issued
by the rack controller.
Decimal A decimal point blinks during communica-
point tion with E2. This occurs several times a
minute. It is a quick way to verify that
communication between the module and
the rack controller has been established.
The decimal is on the lower right-hand
corner of the 7-segment display.
AE8-1337 R1