Emerson E2 Manual do Operador Página 48

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 71
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 47
48
5.1 Demand Cooling Service Procedures
The demand cooling valve injects liquid refrigerant
into the suction manifold to keep the discharge gas
temperature within a safe operating range. Excessive
discharge gas temperature will lead to ring and cylin-
der wear, valve wear and oil coking. Each Intelligent
Store™ Discus® compressor has a temperature
probe in the head to continually monitor the discharge
gas temperature. The injection valve is energized
when the temperature of the probe exceeds the
“Injection Start” temperature. When the probe temper-
ature drops below the “Injection Stop” temperature,
the injection valve closes (is de-energized). Refer to
table 5.2 below for reference temperatures by model.
Note that the temperatures shown for 2D and 3D
5. Maintenance Procedures for
Intelligent Store™ Discus®
Compressors
Emerson Climate Technologies, Inc. requires that all
customers review the recommended guidelines in the
published Application Engineering Bulletins, and
ensure that best engineering practices are followed in
the use of Copeland® brand compressors. Emerson
Climate Technologies, Inc. Application Engineering
Bulletins can be found on our website,
EmersonClimate.com under the section titled “Online
Product Information”. The advice and conclusion by
Emerson Climate Technologies, Inc. represents our
best judgment under the circumstances, but such
advice given and/or conclusion made, or results
obtained shall be deemed used at your sole risk.
Reference Drawing of 2D / 3D Enclosure and Accessories
TEMPERATURE SENSOR
GROUND SCREW
LOW PRESSURE CUTOUT SWITCH AND CONNECTOR
White Dot in Center
Blue Wire Harness (LPCO)
HOUSING COVER NUTS
SCREWS “A”
FRONT CONTROL BOX
HARNESS ANCHOR
HIGH PRESSURE CUTOUT SWITCH AND CONNECTOR
Red Dot in Center
Red Wire Harness (HPCO)
DISCHARGE TEMPERATURE PROBE
Black/White Harness
Attach Green Wire to Ground Screw
SCREW “B”
SIDE BOX
DEMAND COOLING
SOLENOID COIL
Brown Wire Harness
(Liquid Injection)
HARNESS CONNECTORS
To Remove: Depress 2 tabs before pulling
To Install: Push in until connector “snaps”
Install Torque
25-30 ft-lb
Figure 5.1 2D/3D Enclosure Label
Head Probe
Location
3D
Standard ISD & Standard
Head Temperature (°F)
Standard
Demand
Cooling
2D/3D
ISD
4D
ISD
Maximum (Trip)
Reset
Liquid Injection Start
Liquid Injection Stop
310
NA
292
282
280
250
266
264
310
268
292
282
4D
Figure 5.2 Head Temperature Comparison
ISD
AE8-1337 R1