Figure 3.11 ISD Summary Screen
Select the compressor that you wish to rename and
Press F5 (Setup). The ISD Compressor Setup Screen
should be displayed as shown in figure 3.12. Key in
the desired text for the new module name. Additional
information for this compressor may be entered in the
category for Long Name.
Figure 3.12 ISD Setup Screen (General)
3.5 Proofing
Proofing verifies that the compressor is turning ON
and OFF as commanded by the E2 rack controller.
This is accomplished by comparing the run command
status from the E2 with the built in proof checking out-
put of the module. In the event that a compressor fails
proofing, the E2 can call on another compressor to
satisfy demand. To enable proofing, follow these
steps:
1. Press menu to open the Main Menu.
2. Press 5 (Configured Applications).
3. Press 1 (Suction Groups).
4. Highlight the appropriate suction group and press
F5 (Setup).
5. Press F2 (Next Tab) until the Comp Setup tab is
highlighted.
6. Select Yes under the Proof column.
7. Press F2 (Next Tab) until the More tab is high-
lighted. Once the More tab has been selected, the
display should look like figure 3.13.
8. Press F3 (Edit).
9. Press 1 (Alternate I/O Formats).
10. Press 2 to select the Controller / Application /
Property format.
The ISD module has built in proofing detection, so it
is considered the controller for this function. Using
the F4: Lookup key, select the appropriate ISD mod-
ule under controller, the appropriate ISD module
under application, and COMP RUN PROOF under
output.
Note: The COMP RUN PROOF selection will not be
displayed on the Suction Group Setup screen unless
proofing has been enabled by selecting Yes under the
Proof column on the Comp Setup tab.
Figure 3.13 Suction Group Setup Screen
(Proof Setup)
3.6 Welded Contactor
E2 controllers loaded with version 2.21 and later
firmware no longer require special instructions for
welded contactor setup. These associations are
performed automatically by the E2 when the steps in
section 3.3 (Configuring Associations) are performed.
3.7 Failsafe Operation
As with other devices controlled by the E2, each
module may be programmed to operate independent-
ly in the event that communications are lost. The
normal modes of operation are compressor ON or
AE8-1337 R1